background image

GIRA

Info

Combination sensor

Installation Instructions

Combination sensor

9/06

Page 2 of 5

Important:

Check the place of installation for optimal reception of 
the DCF77 time signal.
Reflexions can cause reception interference.
If no interference-free reception is possible, change 
the place of installation by a few meters until the com-
bination sensor receives the time signal without inter-
ference (see chapter „Antenna orientation“).

e

Connection

• The combination sensor is provided with a 10 m-

long connecting cable.
The cable may be extended up to 50 m max. (re-
commended cable: LiYCY 6 x 0.25 mm

2

, shielded).

• Connect the combination sensor to the weather 

station (FIG. 

f

):

(a) pink: 

supply AC/DC 24 V, 600 mA

(b) grey: 

supply ground

(c) green-yellow: shield
(1) green: 

system voltage DC 24 V, > 15 mA

(2) yellow: 

data

(3) white: 

sync.

(4) brown: 

system ground

• If possible, connect the shield of the combination 

sensor (yellow-green, (c)) to earth potential (not to 
GND!). If this is not feasible, the shield must remain 
unconnected.
When the shield is connected with GND, trouble-
free operation of the device cannot be guaranteed.

f

Commissioning

Commissioning includes logging in of the combination 
sensor at the weather station and pointing of the an-
tenna for best reception.
This can be done without a project and before final in-
stallation (e.g. at the workshop).

Log-in of the combination sensor

• Switch on the power. The combination sensor con-

firms that it is ready for operation by two brief tones 
repeated every 5 s (FIG. 

g

).

g

5 s