background image

GIRA

Info

Weather station

Installation Instructions

Weather station

9/06

Page 3 of 4

Power supply of sensors connected 

• The connected sensors can be supplied from ter-

U

s

 and GND (see fig. 

c

). These terminals 

are provided in duplicate and internally intercon-
nected.

• The total current consumption of all sensors sup-

plied this way must not exceed 100 mA.

• In the event of overload or short-circuit between 

+U

s

 and GND, the power will be switched off. After 

removal of the fault, the power is switched on again 
automatically.

• Sensors connected can also be supplied externally 

(e.g. if their current consumption exceeds 100 mA). 
In such case, they must be connected between ter-
minals K1... K4 and GND.

Attention:
U

s

 and GND must not be interconnected with the 

corresponding terminals of another device (risk 
of irreparable damage.

Sensors suitable for connection

For any of the following transducers, the software pro-
vides preset values. 

If other sensors are used, the parameters to be set 
must be determined beforehand.

Commisioning

After switching on the device for the first time, the 
weather station starts a module scan (status LED: 
‘Orange / on’).
As a new device comes by default without configura-
tion, the status LED shows then ‘Red / quickly blink-
ing’.

After connection, a combination sensor is ready for 
operation (as programmed in the weather station).

After downloading a project configuration into the 
weather station, the status LED shows ‘Green / on’.

Status LED

OFF: 

no power supply

Orange/ON: weather 

station 

scanning

Red/slowly blinking:

error: undervoltage at combi-

nation sensor connec-
tion / short-circuit U

s

Red/quickly blinking: error: no project configuration/
 false 

parameters

Green/slowly blinking: address assignment, scan

completed, configuration OK

Green/quickly blinking:  parameter download into

 combination 

sensor

Green/ON: scan 

completed, 

everything OK

Slowly blinking = 1/s; quickly blinking = 2/s

Type

Use

Model

Order 

No.

Wind, brightness,
Twilight, rain

outdoor Combination 

sensor

1025 00

Brightness

outdoor WS 10H

0576 00

Twilight

outdoor WS 10D

0572 00

Temperature

outdoor WS 10T

0577 00

Wind

outdoor WS 10W 

0580 00

Rain

outdoor WS 10R

0579 00