Leak Sensor

 

Operating Instructions

 

 

 

Connecting zero-voltage contact 

1. Deenergise device 

2.  Pull off cover 

3.  Replace blind plug (5) with screwed cable gland (6) 

4.  Insert cable through gland 

5.  Connect cable for zero-voltage contact to terminal block (7) 

Contact via terminal 2 and 3: 

Closed in case of alarm 

Contact via terminal 1 and 3: 

Open in case of alarm 

6. Tighten gland 

7.  Screw on cover 

 
 

Alarm test 

 

Immerse sensor in water. 

 

Ö

  LED alarm (3) red and acoustic signal. 

 

Dry sensor following contact with liquid. 

 
 

Technical data 

Power supply: 

230 V AC / 50 Hz / 1.2 VA 

Ambient temperature: 

0 - 60 °C 

Display Operation: 

LED 

green 

 

Alarm: 

LED red and acoustic signal 

Zero-voltage contact: 

AC 230 V/1,800 VA 

 

DC 100 V/300 W 

Construction: 

Polyester housing IP 65 

Protection class: 

II (protective insulation) 

Dimensions: 

110 x 75 x 55 mm 

Connection cable length: 

1.5 m 

Sensor cable length: 

2 m 

 
 

Directives/Standard 

EC EMC Directive 89/336/EEC 
 
 
 
 
 
 
 
 
 
 
 
 
 
 