Figure 4.5 Connection area of inverter(

Fuse type

)

DC1+

DC1-

DC2+

DC2-

L1 L2 N

.13.

4. Installation

Please refer figure 4.5 and 4.6 to connect the DC1 and DC2 in the DC terminal of inverter,

then connect the array mounting bonding conductor to two “PE” terminal of DC side. The 

DC wire connected to DC terminals (shown in Figure 4.5 and 4.6) is recommended 

AWG12-8. For fuse type inverter KLM-20 of Cooper Bussmann or the same type, only 

professional can replace it.

Connect grid side of inverter:

The inverter is suitable for 208V and 240V grid. Please see table 4.1 to connect cable to 

inverter terminals. Due to inverter monitors voltage between L1 and L2, Neutral could be 

either connected or not for 240V grid.  Ground must be connect to the PE terminal. The 

cable for grid connection to AC terminals (“L1”, “L2”, “N” and “PE”) is recommended for 

AWG 4-8. For fuse type inverter, KLM-30 of Cooper Bussmann or the same type could be 

used, only professional can replace it.

Before electrical connection Please make sure below steps are strictly followed:

a.  Switch the Grid Supply Main Switch (AC) OFF.

b.  Switch the DC Switch OFF.

.12.

4. Installation

Terminal connections:

Before connection, please make sure the polarity of the output voltage of PV array 

matches the

DC+

and

 “

DC-

symbols.

Warning

Before connecting inverter, please make sure the PV array open circuit voltage is 

within the limit of the inverter. Otherwise the inverter could be damaged. The 

maximum allowable input short circuit current limit of the photovoltaic array for each

MPPT input channel is 10Adc for the 1-3.6kW models and it is 15Adc for the

 

4-5kW 

models.

Please don’t connect PV array positive or negative pole to the ground, it could 

cause serious damages to the inverter

Please use qualified DC cable for PV system. 

Fuse type

 connection:

Strip the end of wire about 10mm, loose the screw on the terminal, then insert the wire 

into the terminal. Tight the screws with the torque of 5Nm.

Non-Fuse type

 connection:

Strip the end of wire about 18mm. Use a slotted screwdriver, insert to the end of the 

terminal A and insert the wire into the terminal B. Loose the screwdriver, the cable will be 

fixed in the terminal.

Figure 4.6 Connection area of inverter(

Non-Fuse type

)

Terminal A

Terminal B

Connect PV side of inverter:

For fuse type: Damage to the inverter through the use of fuses as disconnecting
units in the output circuit of the inverter.

WARNING:

Damage to the DC Disconnect due to enlarged knockouts.
Enlarged knockouts enable moisture to penetrate the DC Disconnect which
could damage electronic components in the DC Disconnect.

Note:

Содержание Solis Series

Страница 1: ...Xiangshan Ningbo Zhejiang 315712 P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 Email info ginlong com Web www ginlong com Please record the serial number of your inverter and quote this whe...

Страница 2: ...ont Panel Display 3 2 LED Status Indicator Lights 3 3 Keypad 3 4 LCD 4 Installation 4 1 Select Location for the Inverter 4 2 Mounting the Inverter 4 3 Electrical Connections 5 Start Stop 5 1 Start the...

Страница 3: ...S Solis 5K 2G US Figure 1 2 Bottom side view DC Switch Water drill hole DC input AC input RS 485 Wiring box LCD display 4 buttons LED lights 6 Operation 6 1 Main Menu 6 2 Information 6 3 Settings 6 3...

Страница 4: ...WARNING WARNING symbol indicates important safety instructions which if not correctly followed could result in serious injury or death Improper use may result in potential electric shock hazards or b...

Страница 5: ...To startup the inverter the Grid Supply Main Switch AC must be switched on before the solar panel s DC isolator shall be switched on To stop the inverter the Grid Supply Main Switch AC must be switche...

Страница 6: ...talled in a confined space 9 NOTE Nothing should be stored on or placed against the inverter 300mm 500mm 500mm 300mm 300mm 300mm 300mm Figure 4 1 Inverter Mounting clearance 3 3 Keypad 3 4 LCD There a...

Страница 7: ...2 The steps to mount the inverter on the wall are given as follows 1 Locate the wall studs in the desired location and align the wall mount bracket over the studs Mark the mounting holes For masonry...

Страница 8: ...of the output voltage of PV array matches the DC and DC symbols Warning Before connecting inverter please make sure the PV array open circuit voltage is within the limit of the inverter Otherwise the...

Страница 9: ...on local requirement the inverter will start to generate power The green LED will be on continually and the LCD displays GENERATING WARNING Do not touch the surface when the inverter is operating It m...

Страница 10: ...n Menu Pressing the ENTER key locks Figure 6 2 a or unlocks Figure 6 2 b the screen 5 2 Stop the Inverter Figure 6 2 Locks and Unlocks the Screen of LCD b a 17 16 6 Operation 6 1 Main Menu During norm...

Страница 11: ...n Menu The screen will require the password as below The default password is 0010 Please press down to move the cursor press up to select the number 18 6 3 Settings The following submenus are displaye...

Страница 12: ...access the following options 1 Select Standard 2 Grid ON OFF 3 New Password 4 Calibrate Energy NOTE To access to this area is for fully qualified and accredited technicians only Please follow 6 4 to...

Страница 13: ...integrate with AFCI module which can detect the arc in DC circuit If arc fault happen it can only be removed manually During start up inverter will check AFCI module If the check is OK inverter will...

Страница 14: ...8 1 Alarm Message OV G V UN G V OV G F UN G F G IMP NO GRID OV DC OV BUS UN BUS GRID INTF INI FAULT OV TEM GROUND FAULT Failure description Over grid voltage Under grid voltage Over grid frequency Un...

Страница 15: ...Solis 1 5K 2G US 26 NEMA 4X 70 400Vdc THD 3 96 8 13 F 140 F 339W 657H 164D mm 13 3W 25 9H 6 5D inch 9 8kg 21 6lb CAN CSAC22 2 N107 1 UL1741 UL1998 UL1699B FCC part 15 Class B CAN CSAC22 2 N107 1 UL17...

Страница 16: ...4 for240V rated Solis 3 6K 2G US 29 2 2 2 2 THD 3 THD 3 97 5 97 5 339W 657H 172 5D mm 13 3W 25 9H 6 8D inch 15kg 33 1lb 15kg 33 1lb 339W 657H 172 5D mm 13 3W 25 9H 6 8D inch NEMA 4X 13 F 140 F NEMA 4X...

Страница 17: ...ed Solis 4K 2G US 30 THD 3 THD 3 97 8 97 8 339W 657H 172 5D mm 13 3W 25 9H 6 8D inch 17kg 33 1lb 17kg 33 1lb 339W 657H 172 5D mm 13 3W 25 9H 6 8D inch NEMA 4X 13 F 140 F NEMA 4X 13 F 140 F CAN CSAC22...

Страница 18: ...183 228 for208V rated 211 264 for240V rated Solis 5K 2G US 2 1 and 2 THD 3 97 8 17kg 33 1lb 339W 657H 172 5D mm 13 3W 25 9H 6 8D inch NEMA 4X 13 F 140 F CAN CSAC22 2 N107 1 UL1741 UL1998 UL1699B FCC...