Dimensions (W*H*D)
Weight
1065*567*344.5mm
84kg
Max. DC input voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
MPPT number/Max input strings number
Rated grid voltage (Volts)
Rated grid output current (Amps)
Power Factor (at rated output power)
Max.efficiency
EU efficiency
Model
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Cooling concept
Max.operation altitude
1100
10*26
10*40
10/20
50/60
98.7%
98.3%
Transformerless
<
2W
-25
℃...
+60
℃
0~100%
IP66
Intelligent redundant cooling
4000m
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
600
110000
121000
121000
167.1/158.8
183.8
THDi (at rated output power)
<3%
Start-up voltage (Volts)
Max short circuit input current (Amps)
Rated DC voltage (Volts)
Rated grid frequency (Hertz)
180...1000
195
Solis-110K-5G-SA
Max. output current (Amps)
AC connection
Grid connection standard
DC connection
Display
Communication connections
Warranty
MC4 connector
OT Terminal (max 185 mm²)
LCD, 2×20 Z
RS485, Optional: Wifi, GPRS , PLC
5 years (extand to 20 years)
NRS 097-2-1
Safty/EMC standard
IEC 62109-1/-2, IEC62116 & EN 61000-6-2/-4
3/N/PE, 220/380, 230/400
Operating frequency range (Hertz)
45...55 or 55...65
>
0.99 (0.8 leading - 0.8 lagging)
Noise emission (typical)
≤
65 dBA
10. Specifications
.60.
11. Appendix
11.1 Grid standard selection guide
For different countries and regions, corresponding grid code needs to be selected in the
inverter LCD to meet the requirements of local network provider.
This instruction indicates how to change the grid code and what code should be selected in
different places.
This following list illustrates the grid standard options in the inverter which are subject to
change. It is for your reference only. If customer has any doubts or uncertainty, please
consult Solis service department for confirmation.
To set the correct grid code, please enter the following path:
Advanced Settings -> Password:0010 -> Select Standard
Detailed protection limits can be viewed when choosing the code.
Please select "Save&Send" to enforce the code.
NOTE:
Please check if the grid code setting comply with local requirement.
NO.
1
2
3
4
5
6
7
8
9
10
11
12
Code in LCD
VDE4015
EN50549 PO
EN50549 NL
EN50438 L
France
C10/11
NRS097
CEI0-21
G98
G99
Country/Region
Germany
Poland
Netherland
France
Belgium
South Africa
Italy
UK
UK
Comments
For German Low Voltage Grid.
For Polish Low Voltage Grid
For Dutch Low Voltage Grid
General EN50438 Requirement.
Possible to be used in Austria, Cyprus, Finland,
Czech Republic, Slovenia, etc.
For French Low Voltage Grid
For Belgian Low Voltage Grid
For South African Low Voltage Grid
For Italian Low Voltage Grid
For UK Low Voltage Grid <16A
For UK Low Voltage Grid >16A
-
-
EIFS- SW
Sweden
For Swedish Low Voltage Grid
EN50549L
(EN50549-1)
General EN50549-1 requirement which meets
local requirements of most European countries
.61.