5.10.6 If any values are checked as “Fail”, check the space in the “Fail” column in the
TCT-1000 Battery Capacity Analyzer.
5.10.7 Send the unit back to Teledyne Battery Products for repair or replacement.
6
RECORDS – P/N: TCT-1000; S/N: _________________
TCT-1000 Battery Capacity Analyzer
Record Name
Measured Value
Specification
Pass
Fail
20.0 Volt Cutoff
20.20 – 19.80 Volts
10.0 Volt Cutoff
10.10 – 9.90 Volts
Frequency
(Period for 10 Unit
Increase)
357 sec. – 363 sec.
24 Volt 10 Amp Setting
9.8 – 10.2 mV
24 Volt 50 Amp Setting
49.6 – 50.4 mV
12 Volt 10 Amp Setting
9.8 – 10.2 mV
12 Volt 50 Amp Setting
49.6 – 50.4 mV
Multi-meter Calibration Expiration Date: ________
TCT-1000 Calibration performed as specified by _____________; Date ________