Robust level sensors for varied applications
7010-30-086 Iss. 5
© 2021 Gill Sensors & Controls Limited
6
2. Getting started
The analogue output cable has seven wires:
Red
D.C. Power Supply
Black
Ground
Orange
Primary Output
Yellow
Secondary Output
White
TX
Green
RX
Silver
Drain Wire
The installation of the sensor has different requirements, depending on the analogue output:
Voltage
The sensor is provided with a factory calibrated output range of 0.25 V to4.75 V. The sensor can be
configured to a maximum output range of 0.25 V to 10 V.
The power supply must be at least 0.5V greater than the maximum output voltage required. The
switch output requires a pull-up resistor of 1 kOhm to 10 kOhms.
Current
The current output is 4 – 20 mA. The measurement output requires a 250 Ohm load resistor across the
output. The switch output requires a pull-up resistor of 1 kOhm to 10 kOhms.
Voltage
Current
Supply Voltage
+5 to +32 VDC
+9 to +32 VDC
Over Voltage Protection
>32 VDC
>32 VDC
Supply Current @ 12 VDC
<15 mA
<15 mA
Reverse Polarity Protection
Yes
Yes
Analogue Resolution
10 bit
10 bit
Report Rate
10 Hz
10 Hz