The burner can be put into operation once the gas and electrical installation and assembly work has been
completed.
•
Measure inlet pressure with U-pipe pressure gauge at measuring point "p
E
".
max. 100 mbar (static pressure) for KEV 220, KEV 225
max. 360 mbar (static pressure) for MB407, MB412, MBC300
min. 20 mbar (flow pressure) for -N
min. 35 mbar (flow pressure) for -F
Burner and gas ramp are preset to low output at the factory. This ensures an initial safe start-up of the
burner.
•
Use the adjustment tables to set the burner to the desired nominal output.
For this:
•
Check the nozzle pressure with U-pipe pressure gauge at measuring point "p
G
".
•
Adjust gas pressure and air flow dimension "A" according to adjustment tables.
•
Be sure to check the exhaust gas values (CO, CO
2
and/or O
2
).
•
Depending on the system, the setting values must be corrected.
•
The setting data must be logged once adjustment is complete.
•
Check the gas pressure controller after start-up. Close the ball valve slowly, the burner must switch off
without triggering a fault.
The gas supply line and gas assembly must not subject the burner to tensile, compressive
or torsional forces; since these could adversely affect operational safety.
Exhaust gas values
Natural gas LL+E
Liquefied gas propane 3P
O
2
content
3.5-5.0%
CO
2
content
9-10%
10.5-11.5%
Start-up