INSTALLATION INSTRUCTIONS
The Vent Termination must have a:
Canadian Installations
US Installations
A) Clearance above grade, veranda, porch, deck, or balcony.
12 inches (30 cm)
12 inches (30 cm)
B)
Clearance to window or door that may be opened.
9 inches (23 cm) or
12 inches (30 cm) * * *
C)
Clearance to outside corner.
*
*
D)
Clearance to inside corner.
*
3 feet (91 cm)
E)
Clearance to service regulator vent outlet.
3 feet (91 cm)
3 feet (91 cm)
F )
Clearance to each side of center line extended above
3 feet (91 cm) within a
3 feet (91 cm) within a
meter/regulator assembly.
height 15 feet (4.57 m)
height 15 feet (4.57 m)
above the meter/regulator above the meter/regulator
assembly
assembly
G )
Clearance to non-mechanical air supply inlet to building or
the combustion air inlet to any other appliance.
H)
Clearance to a mechanical air supply inlet.
6 feet (1.82 m)
* * * *
I )
Clearance above paved sidewalk or paved driveway
located on public property.
J)
Clearance under veranda, porch, deck, or balcony.
12 inches (30 cm)**
12 inches (30 cm)**
K)
Clearance to permanently closed window.
*
*
L)
Vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 2 feet (61 cm)
*
*
from the centerline of the terminal.
M)
Clearance to unventilated soffit.
*
*
*
Clearance in accordance with local installation codes and the requirements of the gas supplier.
For Canadian and US installations, the vent shall not terminate above a paved driveway that is located between two single family dwellings and serves both dwellings.
** The veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.
*** 9 inches (23 cm) for appliances with 10,000 Btu/h to 50,000 Btu/h inputs and 12 inches (30 cm) for appliances greater than 50,000 Btu/h.
**** The vent terminal must terminate at least three (3) feet (91cm) above any forced air inlet duct located within ten (10) feet (3.05m).
AREA WHERE TERMINAL
IS NOT PERMITTED
OPERA
BLE
FIXE
D
CLOS
ED
OPER
ABLE
FIXE
D
CLOS
ED
AIR SUPPLY
INLET
INSID
E CO
RNER
DETA
IL
C
K
B
B
I
B
L
M
F
E
B
B
B
A
J
H
G
D
ZONE OÙ L'INSTALLATION
DU "TERMINAL" EST INTERDITE
OPÉR
ABLE
OPÉR
ABLE
FERM
É EN
PERM
ANEN
CE
ALIMENTATION
D'AIR FRAIS
DÉTAIL D'UN
COIN
INTÉ
RIEU
R
B
B
B
B
B
B
A
FERM
É EN
PERM
ANEN
CE
TERMINAISON
D'ÉVENT
VENT
TERMINAL
NONMECHANICAL
AIR SUPPLY
ALIMENTATION
D'AIR FRAIS
VENTILATEUR
D'AIR FORCÉ
MECHANICAL
AIR SUPPLY
C
K
I
B
L
M
F
E
J
H
G
D
Figure 2
12 inches (30 cm)
9 inches (23 cm) or
12 inches (30 cm) * * *
7 feet (2.13 m) 7 feet (2.13 m)
WARNING
DANGER
In freezing weather, check for snow accumulation
around the water heater vent and air intake terminals
where they pass through the outside wall. The open
ends of the terminals must be installed at least 12
inches (30 cm) above the highest anticipated snow-
fall to prevent blockage by snow.
WARNING
DANGER
Check that all openings and gaps in the outside
wall near and around where the vent and air
intake pipes pass through the exterior wall are
sealed to prevent infiltration of combustion
products into the building.
12 inches (30 cm)