background image

20 

 

Flow rates 
Summer Delivery 
Temp. Winter 
Delivery Temp. Free 
Cooling Temp. 
Modulating Valve 
Winter Integr. 
Season Source 
Compr. in 

TIME SLOT SETTING 

The user can set time slots for the automatic activation of exchange and air flow rate 
attenuation; attenuation is a convenient function to reduce the noise from air movement. 

 

HOW TO SET A TIME SLOT 
From the menu screen, select “Exchange hours” or “Attenuation hours” based on the 
desired function and press 

There  are  4  time  slots,  each  with  a  start  time  and 
an end time on the same line. 
To set a time slot, move the cursor on the start 
time and press 

E

: the screen will display a time 

that can be changed using 

and 

; press 

again to confirm. 
Repeat the same procedure to set the end time; 
once both times have been defined, the time slot 
will be set. 

 

HOW TO SET A TIME SLOT 
To delete a time slot, set the start and end time on the same value, the times will be deleted 
and the line will display dashes only. 

 

 

HOW TO SET THE CURRENT TIME OR SEASON 

 

Changing the current time: 

from the setting menu, select “Set time”; use the 

button to 

select the hour or minutes and then change the time using 

and 

. Press 

once again or 

to confirm the desired value  

 

Changing the current season: 

from the setting menu, select “Set 

season”;  

the current value is immediately displayed and can be changed using 

and

Press 

once again or      to confirm the desired value  

 

 

TECHNICAL SETTINGS 

 

To access the technical settings menu enter the 4-digit password; use the number buttons one 
at a time, then press 

E

 to display the technical settings menu. 

The captions below are all submenu entries. Select any caption and press 

to display the 

operational screen of the selected entry. 

start time 

end time 

Exchange time 
slot:

 

--:-- 

--:-- 

--:-- 

--:-- 

Содержание KDVRWY300

Страница 1: ...XCHANGE AND HEAT RECOVERY 12 2021 INDEX page TRANSPORT AND STORAGE 2 DESCRIPTION AND MAIN COMPONENTS OF THE UNIT 2 DIMENSIONS 4 INSTALLATION 4 CONNECTIONS 6 OPERATION DESCRIPTION 9 START UP AND TESTIN...

Страница 2: ...tacked one on top of the other Ideal environment conditions 10 C 50 C relative humidity lower than 90 NOTE Manual handling must comply with the laws in force DESCRIPTION AND MAIN COMPONENTS OF THE UNI...

Страница 3: ...r o cooling compressor p hydraulic connections q condensation drains r electric board Construction characteristics Cooling compressor Hermetic alternative monocylindrical Cooling gas R134a 560g eq CO2...

Страница 4: ...of this user manual The machine contains pressurized cooling gas Vent the room in case of gas leaks from one or multiple units The gas contained in the units may create toxic components in case of fir...

Страница 5: ...max 18 C Electric power 10 A 230V 50Hz 1ph Condensation drain Flow rate 15 l h Min slant 3 2 siphons required h 40 mm Aeraulic ducts Min diameter same as unit nozzles The losses of pressure inside th...

Страница 6: ...ves inside the chilled water pipes to section the system from the machine After connecting the circuit to the system test the water seal of the connections and the unit to prevent damages to the area...

Страница 7: ...anned by qualified electric planners the wire must in any case feature a 3x1 5 sq mm min section F N PE The picture below shows the connection terminals available The electric supply must be provided...

Страница 8: ...unication line between the control panel and the KDVRWY300 unit a 120 Ohm W terminal resistance must be installed between terminals A and B of the control panel This should be fitted with tape on the...

Страница 9: ...flows inside the unit the exchange air flow with heat recovery through the counter current air air recuperator 1 and the room air recirculation flow The exchange and recirculation flows can be either...

Страница 10: ...The water supplied coil 3 fed by the radiant system pre cools the air the cooling evaporator 4 provides air cooling and in turn dehumidification The cooling circuit includes two condensers with parall...

Страница 11: ...circuit loss of pressure kPa 8 Power absorbed by the delivery fan min max W 15 70 Delivery fan flow rate min max m3 h 80 300 Delivery fan useful hydraulic head Pa 120 Power absorbed by the ejection f...

Страница 12: ...1 39 3 29 9 1953 1720 1467 3166 2767 2351 431 457 482 24 65 12 15 18 3358 2945 2504 1818 1654 1488 1540 1291 1016 53 2 44 6 35 1 2107 1877 1621 3270 2881 2465 434 458 483 26 55 12 15 18 3369 2952 251...

Страница 13: ...of operation is in progress but the compressor is not controlled yet because it is on hold or malfunctioning The functions available through digital inputs are current season exchange with heat recove...

Страница 14: ...damper 9 when available is open both fans are ON the compressor is ON and the entire coil unit treats the inflow air The air flow rate of the inflow air can be set between 160 and 300 mc h while the e...

Страница 15: ...low rate can be adjusted through an external 3 way valve optional RECIRCULATION ONLY EXCHANGE RECIRCULATION Damper 10 is open and modulating damper 9 when available is open both fans are ON and the wa...

Страница 16: ...nic card the digital inputs of the various functions the two digital relay outlets that activate a circulation pump and a failure signal CONTROL PANEL CONNECTION ModBus CONNECTION this should be perfo...

Страница 17: ...been assembled Exchange Air exchange with the corresponding flow rate using the heat recuperator Cooling Displayed when summer is selected the dehumidification cooling compressor is turned ON and the...

Страница 18: ...e triangle cursor to the upper line To move back to the previous screen press The initial screen displayed when the unit is ON will be the following current time current season Initial screen The init...

Страница 19: ...E the user can activate the control displayed by YES lock the control displayed by NO or cancel the setting confirmed by two dashes After confirming the setting with E the control duration will be dis...

Страница 20: ...time once both times have been defined the time slot will be set HOW TO DELETE A TIME SLOT To delete a time slot set the start and end time on the same value the times will be deleted and the line wi...

Страница 21: ...r delivery temperature can be adjusted while only the hydraulic pump control relays can be activated if there is no modulating valve Season source To decide if the season must be entered by digital in...

Страница 22: ...nt by the electronic card on the unit There are two types of messages and they are all coded with a multiple of 2 Failure messages signaling a failing sensor Alarm messages signaling an anomalous oper...

Страница 23: ...isk just enter the integration input to restart the unit The other alarms are self deleted when the related issue is solved The control panel displays only one message in case of multiple alarms the d...

Страница 24: ...o nell ambiente dell apparecchiatura o lo smaltimento abusivo della stessa sono puniti dalla legge EN IMPORTANT INFORMATION FOR CORRECT DISPOSAL OF THE PRODUCT This product falls into the scope of the...

Страница 25: ...T WITH AIR EXCHANGE AND HEAT RECOVERY 05 2022 INDEX TRANSPORT AND STORAGE 2 DIMENSIONS 4 INSTALLATION 4 CONNECTIONS 6 OPERATION DESCRIPTION 9 START UP AND TESTING 12 CONTROL PANEL 16 DIAGNOSTICS 22 MA...

Страница 26: ...rs before installing the machine The parcels must be stored upright and in horizontal position and up to three parcels can be stacked one on top of the other Ideal environment conditions 10 C 50 C rel...

Страница 27: ...tchboard for control and management LEGEND a air delivery b delivery fan c ejection fan d foul air ejection e room air recirculation f exchange air vacuum g foul air vacuum h damper for separation fro...

Страница 28: ...of this user manual The machine contains pressurized cooling gas Vent the room in case of gas leaks from one or multiple units The gas contained in the units may create toxic components in case of fir...

Страница 29: ...C Electric power 10 A 230V 50Hz 1ph Condensation drain Flow rate 15 l h min slant 3 2 siphons required h 40 mm Aeraulic ducts Min diameter same as unit nozzles The losses of pressure inside the ducts...

Страница 30: ...pipes Insert shut off valves inside the chilled water pipes to section the system from the machine After connecting the circuit to the system test the water seal of the connections and the unit to pr...

Страница 31: ...the nozzles is approx 1 mm shorter than the nominal diameter ELECTRIC CONNECTIONS WIRE SECTION The electric supply line and the section devices must be selected by qualified electric planners the wir...

Страница 32: ...he control panel and the KDVRAY360 unit be longer than 25 m a 120 Ohm W terminal resistance must be installed between terminals A and B of the control panel The resistance should be fitted with tape o...

Страница 33: ...n the flow rates and the type of treatment desired for the inflow air The unit also includes a duct controlled by a motorized damper to vacuum the external air without passing through the recuperator...

Страница 34: ...s process the unit exploits the ejected foul air and an additional integration flow of external air The two electronic expansion valves E enable to distribute the condensation heat between the inflow...

Страница 35: ...l h 360 Water circuit loss of pressure kPa 12 Power absorbed by the delivery fan min max W 40 170 Delivery fan flow rate min max m3 h 90 360 Delivery fan useful hydraulic head Pa 200 Power absorbed b...

Страница 36: ...flow rates normal and integration delivery temperature for each season time slots for automatic exchange max 4 time slots for flow rate attenuation max 4 The operator can also read the values of the u...

Страница 37: ...e setting temperature Should it be necessary to dispose the exceeding heat the ejection fan vacuums and ejects the external air flow heated by the exhaust coil The compressor and both fans are ON The...

Страница 38: ...are working and perform air exchange the external air is heated first by the recuperator through the ejected air and then by the hot water circulating inside the finned coil is vacuumed and at the se...

Страница 39: ...air flow rate can be set between 90 and 360 m3 h while the exchange share can be set between 90 and 220 m3 h The fans are both working the damper of the inflow external air is closed and the bypass da...

Страница 40: ...the various functions the two digital relay outlets that activate a circulation pump and a failure signal MODBUS CONNECTION the connection is carried out with 4 threads 2 for the 24VDC supply to the...

Страница 41: ...setting limits Attenuation The unit works with the same flow rates of attenuation set by default on lower values compared to normal operation to reduce noise This function is convenient if the user w...

Страница 42: ...atus and move the triangle cursor to the upper line To move back to the previous screen press The initial screen when the unit is ON will be the following current time current season Initial screen Th...

Страница 43: ...cursor on the line of the desired control using or press E to confirm the function YES block the function NO or cancel the setting two dashes After confirming the setting with E the control duration...

Страница 44: ...ined the time slot will be set HOW TO SET A TIME SLOT To delete a time slot set the start and end time on the same value the times will be deleted and the line will display dashes only HOW TO SET THE...

Страница 45: ...ion Winter Delivery Temp Air delivery temperatures in winter mode one for the neutral air function and one for the heating integration function Temp Free Cooling temperatures that limit the free cooli...

Страница 46: ...ged Sens Failure 512 Differential pressure sensor for exchange air Sens Failure 1024 Differential pressure sensor for ejection air Alarm messages Message Meaning Alarm 1 Unit with no cooling gas perma...

Страница 47: ...luded filters may not be suitable Install air filters outside the unit based on the system needs Remove the air filters DEMOLITION AND DISPOSAL In case of demolition of the dehumidifier remember that...

Страница 48: ...UCT This product falls into the scope of the Directive 2012 19 EU concerning the management of Waste Electrical and Electronic Equipment WEEE This product shall not be dispose in to the domestic waste...

Страница 49: ...ND DEHUMIDIFICATION MODEL KDVRAY500 05 2022 SUMMARY pag TRANSPORT AND STORAGE 2 MACHINE DESCRIPTION AND INTENDED USE 2 DIMENSIONS 5 POSITIONING AND FIXING 6 CONNECTIONS 8 CONTROL UNIT CONNECTIONS 16 C...

Страница 50: ...WARNING The machine contains pressurized refrigerant gas In the event of a gas leak from one or more machines ventilate the room In case of fire the gas contained in the machines can develop toxic com...

Страница 51: ...ates and the type of treatment to be carried out on the injected air There is also a duct controlled by a motorized shutter which allows the intake of external air without passing through the recupera...

Страница 52: ...e from 300 mc h up to 500 mc h fresh air flow rate settable from 160 up to 300 mc h free cooling renewal flow rate settable from 160 to 300 mc h Please note the ambient flow rate is equal to the sum o...

Страница 53: ...outwards In carrying out this process the machine uses both exhaust stale air and an additional air flow coming from outside The two electronic expansion valves E allow to distribute the condensation...

Страница 54: ...rous situations in the presence of electricity After filling the system with water it is advisable to check that not only the connections but also the machine hydraulic circuit are watertight as these...

Страница 55: ...EPLACEMENT OF THE WHOLE UNIT It is necessary to leave spaces free of obstacles around the machine according to the measurements indicated in the figure below These spaces including that occupied by th...

Страница 56: ...to the system a water tightness check must be carried out on both the connections and the machine in order to avoid any damage for the area below the machine Condensate drain There are three condensa...

Страница 57: ...e nominal diameter ELECTRICAL CONNECTIONS CONDUCTOR SIZE The electric power supply line and the isolating devices must be decided by qualified staff responsible for the electrical design In any case t...

Страница 58: ...OF THE CONTROL PANEL It is necessary to insert a termination resistance of 120 Ohm W between terminals A and B of the control panel The resistance is fixed with adhesive tape on the back of the contr...

Страница 59: ...apacity for water circuit external air 35 C 50 RH max flow rate for delivery and intake W 2050 Power consumption of the inlet fan min max W 20 160 Inlet fan air flow rate min max mc h 160 500 Availabl...

Страница 60: ...ntilation and Ventilation Recirculation mode standard air supply temperature and air temperature for heating and cooling automatic time slots for fresh air ventilation max 4 time slots for flow rate a...

Страница 61: ...d the supply fan are running the room air is dehumidified and supplied into the room at the requested temperature A suitable amount of outdoor air is passed through the condenser finned coil by the ex...

Страница 62: ...water rate is flowing The air is fed back at the requested temperature the supply fan is running the indoor air is heated in the finned coil the supply air flow rate can be set from 300 to 500 m3 h Th...

Страница 63: ...be delivered at the requested temperature by the hot water coil The supply air flow rate can be set from 300 to 500 m3 h the renewal part of it can be set from 160 to 300 m3 h The fans are both runni...

Страница 64: ...communication Use a 4 wire shelded cable minimum cross section 0 5 mmq OUTPUT RELAYS C01 NO1 relay 250V AC 5A is activated when water circulation is needed it can be connected to a pump C01 NO2 relay...

Страница 65: ...eason DI05 integration mode supplying sensible heat In integration mode unless the renewal contact is closed the recirculation function will start up The integration function acts differently accordin...

Страница 66: ...the machine is off the following screen appears To switch from OFF to ON press the button or the button pressing the button E status is confirmed and the cursor moves to the top row to return to the p...

Страница 67: ...rs N the related function you can either choose not to modify the function appears Since the setting has been confirmed after pressing the E button you need to set the duration time of the command The...

Страница 68: ...e that you can change pressing button or button By pressing E the time is confirmed The same procedure can be made to set the end time To delete a time slot you have to set the end time equal to the s...

Страница 69: ...standard mode or heating integration mode Freecooling temperature you can set the values range within freecooling mode will be allowed Freecooling function will be inhibited depending on the outside...

Страница 70: ...air supply Sensor Fault 1024 Failure on the flow sensor for stale air Sensor Fault 2048 Failure on the flow sensor for renewal air Alarms messages Displayed Meaning Alarm 1 Refrigeration circuit low p...

Страница 71: ...air spigots remove the cover carefully the filters can now be removed and cleaned using soap and water or by blowing with compressed air periodic maintenance consists in cleaning the air filters Pleas...

Страница 72: ...sposal of the product is punishable by law FR AVERTISSEMENTS POUR L LIMINATION CORRECTE DU PRODUIT Ce produit entre dans le champ d application de la directive 2012 19 UE relative la gestion des d che...

Отзывы: