Settings
Domestic hot water temperature (kit GE556Y522)
Set DHW temperature using the thermostatic head (Components- Ref. 10).
The temperature must be set placing a digital thermostat under the outflowing water (factory setting 50 °C).
Turn the thermostatic head to increase or decrease the mixed water temperature referring to the handwheel graduated
tampography.
NOTE.
We recommend installing one or multiple thermostatic mixers downstream to the HIU, especially when kit GE556Y521 is installed.
Electric connections
There is an IP55 electric box (Components - Ref. 23) in the upper right corner of the HIU, including a terminal strip for electric
connection of the circulator, optional thermostats and M-Bus networks for data centralization.
Electric data of recirculation kit circulator GE556Y564
Power supply: 230 V / 50 Hz
Electric power: 3÷4.5 W
M-Bus
To connect the M-Bus data cable to the concentrator, also refer to the datasheet of the thermal energy meter used.
• Periodically check the primary circuit pressure value through the boiler room gauge: it must be kept above 1 bar (pressure
values lower than 1 bar may damage the circulator by cavitation).
• Periodically check sealing elements making sure there are no leaks from joints and glued parts (recommended every two
years).
• Periodically check proper hydraulic operation (recommended every two years).
• Periodically check the efficiency of electric and electronic components (recommended every two years).
Periodical inspections and maintenance