BA_MA_GS125_EN_V1.04
17 / 24
Limit switch GS125
Output
Relay output
Switching voltage:
Switching frequency:
Switching hysteresis:
<250 V AC <2 A <500 VA
<125 V DC <0,2 A <25 W; < 30 V DC <2 A <60 W
5 Hz, max
Approx. 1%
Limit value adjustment
Scale prescision: 2%
Analogue output
4…20 mA
Burden
< 120 Ω, max. (Burden error @ 120 Ω, 0,1% max.)
No galvanic isolation to input signal
Casing
Material
PA6.6, flammability class UL94V-0
Color
light grey
Width
12,5 mm
Dimensions (HxD)
108 x 114 mm
Weight
120 g
Protection class
Casing IP 30, terminals IP 20 BGV A3
Terminals
Screw terminals
Push-In-terminals (spring loaded)
Power Rail
0,2...2,5 mm², AWG 24..14, removable, coded
0,5..1,5 mm², AWG 25..16, double connection
(12A between connections), removable, coded
8A over the entire bus system
(Supply via removable terminals
0,2..2,5 mm², AWG 24..14)
Mounting
DIN Rail mounted, TS35 DIN EN 60715
Functional safety
SIL2 (parameters acc. to EN61508 and SN29500)
Device type
B
HFT
0 (1oo1)
Response time
Standard mode
Error
500ms with temperature measurement
100ms with voltage, current, poti measurement
Error
Standard mode
approx. 2s (self resetting)
Evaluation criteria for supply voltage drops to 0% over 20ms
GS125L, GS125M
Relays
Analogue output
FS
B
Table 6 Technical Data
Содержание Martens GS125L
Страница 1: ...Operating Manual Limit switch GS125L EN Save for later reference ...
Страница 24: ...BA_MA_GS125_EN_V1 04 22 24 Limit switch GS125 Certificate of Conformity ...
Страница 25: ...BA_MA_GS125_EN_V1 04 23 24 Limit switch GS125 Notes ...
Страница 26: ...BA_MA_GS125_EN_V1 04 24 24 Limit switch GS125 Notes ...