4 Configuration
Follow these instructions to configure the functions of the device:
Press button
SET
until the first parameter becomes visible in the.
Switch to the desired parameter by pressing the button
SET
.
Use the button
▲ or ▼ to change a value and use button
SET
to validate the value.
If there is no key pressed within the menu mode within 2 minutes, the configuration will be
cancelled.
All changed settings will be lost!
Changing the device parameters is password protected by factory default. The password
must be set correctly to 185 for entering the menu. The last menu point gives the option to
disable the password protection.
4.1 Password lock
Display
Values
Information
SET
Button ▼ and ▲
Password
For entering the configuration menu the password has to be set to 185.
4.2 Output configuration
To achieve best accuracy the output signal should be at least 50 % of the used
sensor’s measuring range.
Refer to 10 Sensor accuracies on page 15.
Setting the output to 0..1 mbar when using a sensor range of -10..10 will extremely
decrease the accuracy.
Display
Values
Information
SET
Button ▼ and ▲
Unit and range of the pressure display
The unit defines the decimal point position as well as the display range.
Depending on the sensor range some units may not be visible.
bar
mbar
Pascal
hecto Pascal
PSI
Torr (= mmHg)
Output type
Voltage output (0 … 10 V)
Current output (4
… 20 mA, factory default)
Output zero point (low value)
…
Display value for an output value of 4 mA (or 0V)
(Factory default
: Lower measuring range)
Output scale (high value)
…
Display value for an output value of 20 mA (or 10V)
(Factory default
: Upper measuring range)
Output in case of an error
Output is <= 3,6 mA / 0V (factory default)
Output is >= 21 mA / 10,5 V