Switching behaviour TS125...-F, TS225...-F (with error relay)
Input Ch.1 switches Relay A1 and A2
Standard relay A1
Input
Switch INV-
Ch.1
Switch ERR-
Ch.1
Relay A1
open (<0.2mA)
off
off
open
on
off
closed
on or off
on
open
inactive (0.4…1.2mA)
off
on or off
open
on
on or off
closed
active (2.1…6mA)
off
on or off
closed
on
on or off
open
short-circuit (>7mA)
off
off
closed
on
off
open
on or off
on
open
Error relay A2
Input (at Ch.1)
Switch INV-
Ch.2
Switch ERR-
Ch.2
Relay A2
open (<0.2mA)
off
off
open
on
off
closed
off
on
closed
on
on
open
inactive (0.4…1.2mA)
off
on or off
open
on
on or off
closed
active (2.1…6mA)
off
off
closed
on
off
open
off
on
open
on
on
closed
short-circuit (>7mA)
off
on or off
closed
on
on or off
open