16
Display
Description
(entered values are factory settings)
20.0
°
C
Limit value
pre alarm
2.0
°
C
Hysteresis
pre alarm
Analog Output
0..20
> OFF
0.0
°
C
Start
analog output
100.0
°
C
End
analog output
Pre-alarm relay hysteresis
Change of the value in the range
1°C (0.1°C) ... 100°C (100.0°C).
Alarm value (switching point) of the pre-alarm relay
Change of the value in the corresponding measuring range.
Function of the analog output
OFF
Analog output is switched off
0..20
Analog output 0-20mA and/or 0-10V
4..20
Analog output 4-20mA and/or 2-10V
0..20/22
Analog output 0-20mA and/or 0-10V, in case of error 22mA/11V
4..20/22
Analog output 4-20mA and/or 2-10V, in case of error 22mA/11V
3.6/4..20
Analog output 4-20mA and/or 2-10V, in case of error 3.6mA/1.8V
Start value of the analog output
Change of the value in the range
-200°C (-200.0°C) ... 2000°C
(2000.0°C).
End value of the analog output
Change of the value in the range
200°C (-2000.0°C) ... 2000°C
(2000.0°C).