Ghibli PDC series Скачать руководство пользователя страница 9

9

ASSEMBLY PROCEDURE

1. Position the supplied paper template on the wall and using a pencil mark the

position of the hatch to be made in the wall (see the recess outline on the refe-

rence template).

Unusual installation positions must be worked out case by case.

Whenever the paper template has not been provided, see the dimensions

shown in the drawing on Page 14. 

2. Make an opening of adequate depth in the wall bearing in mind that the unit's

recessed section has a maximum depth of 235 mm and a minimum depth of 185

mm (see Figure 3).

3. Consulting the reference measurements provided on the template, drill ade-

quate holes for the suction and expulsion of the air using drill bits.

These holes must slope slightly downward by approximately 0.5 cm from the

inside to the outside in order to prevent rain or dirt from entering the room and

the air conditioner.

3a. Consider the idea of preparing a compartment for the air conditioner's power

supply inside the opening in the wall, making sure that it will not create pro-

blems subsequently during the insertion of the unit.

4. Insert the plastic pipes of diameter and length adequate to the depth of the

wall into the holes drilled for air suction and expulsion, making sure that the

pipe lined with condensate-proof material can be fitted into hole A as shown in

Figure 1.

N.B.: The air inlet and outlet pipes supplied have a maximum length of 400

mm; for this reason, if the depth of the wall is less, these pipes must be cut. For

installations with pipes longer than 400 mm, please contact your nearest

Technical Assistance Center or your Manufacturer's technical/commercial con-

tact person. 

5. Make sure that the air expulsion pipe (hole A in Figure 2) is lined with con-

densate-proof insulation  material along its entire length.

Whenever the kit supplied is not used, remember to internally line the air expul-

sion pipe (to be fitted in hole A in Figure 2) with condensate-proof material for

its entire length.

6. Apply junk rings or appropriately insulated flan-

ges on the pipes in order to guarantee ideal contact

between the air conditioner and the holes (see

Figure 4).

IMPORTANT: the cut flange must be applied near

hole A shown in Figure 2 where the insulated pipe

will be connected. 

854

440

3. BUILT-IN INSTALLATION

IMPORTANT: Make sure that the thickness and type of wall are adequate to flush-mount air conditioner installation.

IMPORTANT: Cordon off the outdoor area immediately beneath the installation area to prevent falling masonry debris or

chunks of plaster from damaging or injuring property and people below. 

Make sure that there are no electric hoses or gas or water pipes inside the parts of the wall to be drilled.
IMPORTANT: THE UNIT MUST BE INSTALLED FOLLOWING THE NATIONAL REGULATIONS.

fig. 1

fig. 2

A air expulsion hole
B air suction hole

7

Wall bracket

115 mm

300 mm

185 mm

fig. 3

A

B

fig. 4

Содержание PDC series

Страница 1: ...INSTALLATION MANUAL GHIBLI PDC DETRAZIONE FISCALE ALTA EFFICIENZA RISPARMIO ENERGETICO INSTALLAZIONE FACILE ENERGIA RINNOVABILE DIMENSIONI COMPATTE FUNZIONE A BASSA TEMPERATURA VENTILAZIONE SILENZIOSA AUTORESTART DI SERIE GAS ECOLOGICO ...

Страница 2: ...2 ...

Страница 3: ...EXPLAIN THE UNIT S OPERATION TO THE CLIENT USING THE OPERATION AND MAINTENANCE MANUAL GIVE THE OPERATION AND MAINTENANCE MANUAL TO THE CUSTOMER THE UNIT INSTALLATION IS FOR QUALIFIED STAFF ONLY THE UNIT MUST BE INSTALLED FOLLOWING THE NATIONAL REGULATIONS THE POWER SUPPLY PLUG MUST BE ACCESSIBLE AFTER THE UNIT INSTALLATION IF THE POWER SUPPLY CABLE IS DAMAGED IT MUST BE SUBSTITUTED EXCLUSIVELY BY ...

Страница 4: ...tion E The rear ventilation grills must be free from obstacles to permit a free flow of air F Make sure that the flow of air expulsed from the rear grills does not disturb the neighbours and is not directed to an area with a continuous passing of pedestrians G The flow of air from the rear grills must not be sent into a closed room because if this expulsed air is injected into an area without free...

Страница 5: ...es all the information found in the respective chapters that explain the various types of installation possible Wall installation page 6 Built in installation page 9 section section Installation to the edge of the wall page 12 section Wall bracket Wall bracket ...

Страница 6: ...pulsion making sure that the pipe lined with condensate proof material can be fitted into hole A as shown in Figure 1 N B The air inlet and outlet pipes supplied have a maximum length of 400 mm for this reason if the depth of the wall is less these pipes must be cut For installations with pipes longer than 400 mm please contact your neare st Technical Assistance Center or your Manufacturer s techn...

Страница 7: ...inside the condensate drainage in order to prevent water from freezing insi de the pipe in low temperature installations Cut the length of pipe as required depending on how far it must protrude outside bearing in mind that it must protrude from the air hosing sealing grill by 1 cm IMPORTANT make sure that the downward inclination of the condensate drainage outwards is in the range of from 4 to 5 f...

Страница 8: ...t be applied to the air circulation pipes As above this particular measure will ensure better unit operation because not only will the air be filtered and therefore the heat exchange system will remain cleaner and maintain yield over a longer period of time but also will prevent the deposit of leaves or other clogging material in the pipes and infiltration by birds or other small animals These gri...

Страница 9: ... The air inlet and outlet pipes supplied have a maximum length of 400 mm for this reason if the depth of the wall is less these pipes must be cut For installations with pipes longer than 400 mm please contact your nearest Technical Assistance Center or your Manufacturer s technical commercial con tact person 5 Make sure that the air expulsion pipe hole A in Figure 2 is lined with con densate proof...

Страница 10: ...event water from freezing inside the pipe in low temperature installations Cut the length of pipe as required depending on how far it must protrude outside bearing in mind that it must protrude from the air hosing sealing grill by 1 cm IMPORTANT make sure that the downward inclination of the condensate drainage outwards is in the range of from 4 to 5 fig 8 slowly pour water into the condensing uni...

Страница 11: ... therefore the heat exchange system will remain cleaner and maintain yield over a longer period of time but will also prevent the deposit of leaves or other clogging material in the pipes and infiltration by birds or other small animals These grills can be quickly removed and cleaned whenever necessary AIR SUCTION VIEW OF AIR CONDITIONER REAR GRILLS AIR EXPULSION CONDENSATE DRAIN 9 8 Installation ...

Страница 12: ...tion the power supply cable must be substituted with a flexible cable with polychloro prene sheath like H05RN F or H07RN F Make sure that there are no electric hoses or gas or water pipes inside the parts of the wall to be drilled IMPORTANT THE UNIT MUST BE INSTALLED FOLLOWING THE NATIONAL REGULATIONS 1 Position the supplied paper template on the wall and using a pencil mark the position of the ha...

Страница 13: ...e resins in order to avoid the water and the insect entrance 5 Place along the frontal A and rear B side a thermal noise proof material thickness 50 mm in order to avoid noise air and heat passage from the unit to the room and outdoor ambient and viceversa see fig 3 6 Condensate drain preparation Assemble the condensate drainage pipe by firmly pushing and twisting it towards the air conditioner se...

Страница 14: ...erating problems short circuits or other malfunc tions to the unit In order to reduce the length of the electric heating element just pull it inside the unit as shown in fig 6 7 7 1 7 2 7 3 Whenever the unit must be removed make sure to first drain the condensate collection tray to avoid annoying water spills During transport always leave the air condi tioner positioned upright on a flat surface a...

Страница 15: ...in the continuity tank could last up to 5 6 hours depending on the ambient humidity When it is exhausted the user can fill the conti nuity tank then the air conditioner restarts working at HIGH EFFICIENCY The Drain exit must be closed the auxiliary Extra drain outlet is connected to the pump in order to recover the dew created on the evaporator and eliminate it by evaporation on the condensers ONL...

Страница 16: ...THE CONDENSATE DRAINAGE AND VENTILATION HOLES THE OUTLINE REGARDS THE UNIT S REAL PERIMETER AND NOT THE OPENING TO BE MADE IN THE WALL WHICH MUST CONSEQUENTLY BE INCREASED BY 10 MM ON EACH SIDE AND 20 MM IN HEIGHT IMPORTANT THESE DIMENSIONS ARE IN MILLIMETERS 304 373 ...

Страница 17: ...lass surface insert adequate vibration damping shims to prevent both the vibration of the structure and the crushing of the condensate drainage pipe Connect to this rubber pipe an extension pipe that permits the excess condensate created by the unit towards a special drain or into a temporary collection tray THAT MUST BE REGULARLY CHECKED AND DRAINED IMPORTANT incorrect installation can cause wate...

Страница 18: ...e heat exchanger clogs When the protection triggers the unit must be accurately cleaned by opening the upper panel and sucking any impu rities present In case of malfunction of the fan repair or replace as required The air conditioner comes with its own power supply cable for connection to the local mains In order to avoid overloads make sure that the electric system s socket voltage and current l...

Страница 19: ...19 ...

Страница 20: ...20 A2B Accorroni E G s r l Via d Ancona 37 60027 Osimo An Tel 071 723991 r a Fax 071 7133153 web site www accorroni it e mail a2b accorroni it ...

Отзывы: