Ghibli PDC series Скачать руководство пользователя страница 17

17

15

6. AUXILIARY CONDENSATE DRAINAGE

Remove the plug from the condensate drainage nozzle positioned at

the lower right as shown in Figure 1, making sure to avoid cutting

your hands and damaging the heat exchanger.

Whenever crushed or damaged wings are observed, straighten them

before switching the unit on.

Pull the electric heating element completely inside the unit.

N.B. NEVER CUT THE ELECTRIC HEATING ELEMENT.

Make the hole for the passage of the auxiliary condensate drainage

pipe in the rear panel; it is masked by insulation material that covers

the plate (Figure 2); cut away the covering with a cutter, paying atten-

tion not to damage the surrounding insulation material.

NOTE: The auxiliary condensate drainage is provided with nozzle

closed. Before use, it is recommended to pierce the nozzle.

Prepare a recess in the wall where the unit will be installed in order to prevent the condensate drainage pipe from raising the air condi-

tioner and preventing the correct elimination of water; whenever the unit rests on a glass surface, insert adequate vibration-damping

shims to prevent both the vibration of the structure and the crushing of the condensate drainage pipe. 

Connect to this rubber pipe an extension pipe that permits the excess condensate created by the unit towards a special drain or into a

temporary collection tray 

THAT MUST BE REGULARLY CHECKED AND DRAINED

.

IMPORTANT: incorrect installation can cause water leakage along the wall.

Whenever the installation of auxiliary condensate drainage is not foreseen, never remove the plug from the  inside of the air conditioner.

N.B.: once this plug is removed, water flows freely from the tray and can damage both the unit and the wall.

Pressing firmly, insert the rubber pipe into the condensate drainage nozzle making sure that it is tightly connected and then

reassemble the unit's rear panel.

Fig. 1 (rear view) - condensate plug position

Fig. 2 (rear view) - preparation of hole for pipe

The first thing to do is remove the five screws in the rear panel's lower right corner near the auxiliary condensate drainage.

When this panel is returned to position, make sure to return these screws to their original positions; the use of screws of insufficient

length can cause serious damage to the unit.

Содержание PDC series

Страница 1: ...INSTALLATION MANUAL GHIBLI PDC DETRAZIONE FISCALE ALTA EFFICIENZA RISPARMIO ENERGETICO INSTALLAZIONE FACILE ENERGIA RINNOVABILE DIMENSIONI COMPATTE FUNZIONE A BASSA TEMPERATURA VENTILAZIONE SILENZIOSA AUTORESTART DI SERIE GAS ECOLOGICO ...

Страница 2: ...2 ...

Страница 3: ...EXPLAIN THE UNIT S OPERATION TO THE CLIENT USING THE OPERATION AND MAINTENANCE MANUAL GIVE THE OPERATION AND MAINTENANCE MANUAL TO THE CUSTOMER THE UNIT INSTALLATION IS FOR QUALIFIED STAFF ONLY THE UNIT MUST BE INSTALLED FOLLOWING THE NATIONAL REGULATIONS THE POWER SUPPLY PLUG MUST BE ACCESSIBLE AFTER THE UNIT INSTALLATION IF THE POWER SUPPLY CABLE IS DAMAGED IT MUST BE SUBSTITUTED EXCLUSIVELY BY ...

Страница 4: ...tion E The rear ventilation grills must be free from obstacles to permit a free flow of air F Make sure that the flow of air expulsed from the rear grills does not disturb the neighbours and is not directed to an area with a continuous passing of pedestrians G The flow of air from the rear grills must not be sent into a closed room because if this expulsed air is injected into an area without free...

Страница 5: ...es all the information found in the respective chapters that explain the various types of installation possible Wall installation page 6 Built in installation page 9 section section Installation to the edge of the wall page 12 section Wall bracket Wall bracket ...

Страница 6: ...pulsion making sure that the pipe lined with condensate proof material can be fitted into hole A as shown in Figure 1 N B The air inlet and outlet pipes supplied have a maximum length of 400 mm for this reason if the depth of the wall is less these pipes must be cut For installations with pipes longer than 400 mm please contact your neare st Technical Assistance Center or your Manufacturer s techn...

Страница 7: ...inside the condensate drainage in order to prevent water from freezing insi de the pipe in low temperature installations Cut the length of pipe as required depending on how far it must protrude outside bearing in mind that it must protrude from the air hosing sealing grill by 1 cm IMPORTANT make sure that the downward inclination of the condensate drainage outwards is in the range of from 4 to 5 f...

Страница 8: ...t be applied to the air circulation pipes As above this particular measure will ensure better unit operation because not only will the air be filtered and therefore the heat exchange system will remain cleaner and maintain yield over a longer period of time but also will prevent the deposit of leaves or other clogging material in the pipes and infiltration by birds or other small animals These gri...

Страница 9: ... The air inlet and outlet pipes supplied have a maximum length of 400 mm for this reason if the depth of the wall is less these pipes must be cut For installations with pipes longer than 400 mm please contact your nearest Technical Assistance Center or your Manufacturer s technical commercial con tact person 5 Make sure that the air expulsion pipe hole A in Figure 2 is lined with con densate proof...

Страница 10: ...event water from freezing inside the pipe in low temperature installations Cut the length of pipe as required depending on how far it must protrude outside bearing in mind that it must protrude from the air hosing sealing grill by 1 cm IMPORTANT make sure that the downward inclination of the condensate drainage outwards is in the range of from 4 to 5 fig 8 slowly pour water into the condensing uni...

Страница 11: ... therefore the heat exchange system will remain cleaner and maintain yield over a longer period of time but will also prevent the deposit of leaves or other clogging material in the pipes and infiltration by birds or other small animals These grills can be quickly removed and cleaned whenever necessary AIR SUCTION VIEW OF AIR CONDITIONER REAR GRILLS AIR EXPULSION CONDENSATE DRAIN 9 8 Installation ...

Страница 12: ...tion the power supply cable must be substituted with a flexible cable with polychloro prene sheath like H05RN F or H07RN F Make sure that there are no electric hoses or gas or water pipes inside the parts of the wall to be drilled IMPORTANT THE UNIT MUST BE INSTALLED FOLLOWING THE NATIONAL REGULATIONS 1 Position the supplied paper template on the wall and using a pencil mark the position of the ha...

Страница 13: ...e resins in order to avoid the water and the insect entrance 5 Place along the frontal A and rear B side a thermal noise proof material thickness 50 mm in order to avoid noise air and heat passage from the unit to the room and outdoor ambient and viceversa see fig 3 6 Condensate drain preparation Assemble the condensate drainage pipe by firmly pushing and twisting it towards the air conditioner se...

Страница 14: ...erating problems short circuits or other malfunc tions to the unit In order to reduce the length of the electric heating element just pull it inside the unit as shown in fig 6 7 7 1 7 2 7 3 Whenever the unit must be removed make sure to first drain the condensate collection tray to avoid annoying water spills During transport always leave the air condi tioner positioned upright on a flat surface a...

Страница 15: ...in the continuity tank could last up to 5 6 hours depending on the ambient humidity When it is exhausted the user can fill the conti nuity tank then the air conditioner restarts working at HIGH EFFICIENCY The Drain exit must be closed the auxiliary Extra drain outlet is connected to the pump in order to recover the dew created on the evaporator and eliminate it by evaporation on the condensers ONL...

Страница 16: ...THE CONDENSATE DRAINAGE AND VENTILATION HOLES THE OUTLINE REGARDS THE UNIT S REAL PERIMETER AND NOT THE OPENING TO BE MADE IN THE WALL WHICH MUST CONSEQUENTLY BE INCREASED BY 10 MM ON EACH SIDE AND 20 MM IN HEIGHT IMPORTANT THESE DIMENSIONS ARE IN MILLIMETERS 304 373 ...

Страница 17: ...lass surface insert adequate vibration damping shims to prevent both the vibration of the structure and the crushing of the condensate drainage pipe Connect to this rubber pipe an extension pipe that permits the excess condensate created by the unit towards a special drain or into a temporary collection tray THAT MUST BE REGULARLY CHECKED AND DRAINED IMPORTANT incorrect installation can cause wate...

Страница 18: ...e heat exchanger clogs When the protection triggers the unit must be accurately cleaned by opening the upper panel and sucking any impu rities present In case of malfunction of the fan repair or replace as required The air conditioner comes with its own power supply cable for connection to the local mains In order to avoid overloads make sure that the electric system s socket voltage and current l...

Страница 19: ...19 ...

Страница 20: ...20 A2B Accorroni E G s r l Via d Ancona 37 60027 Osimo An Tel 071 723991 r a Fax 071 7133153 web site www accorroni it e mail a2b accorroni it ...

Отзывы: