background image

Page 12

Important Notice

!

After the Mains supply has been connected by inserting the CEE plug in the
appropriate socket or turning on the main switch, confirm that the phase rotation
is correct by checking that the door opens when the OPEN push button is
operated.
If the door closes when operating the OPEN push button reverse two phases
at the terminal X1.

PHASE ROTATION

DANGER! To the life and health through electric shock.

Before changing phase rotation the mains supply must be switched OFF.

Three-phase 3 x400 V AC, N, PE

Star connection

Three-phase 3 x230 V AC, PE

Delta connection

Single-phase 1x230 V AC, N, PE

symmetrical winding

Single-phase 1x230 V AC, N, PE

asymmetrical winding

Important note!

For 3x400V AC PE no
neutral, the brake
rectifier must be
connected between
terminal V and star-
point terminal.

brown

brown

supply for
brake
rectifier

blue

supply for
brake
rectifier

MOTOR CONNECTION (internal wiring)

blue

On several ELEKTROMATEN

®

 the connection U1 und V1 on the  motor-plug are

interchanged.

Содержание Elektromaten TS 956

Страница 1: ...Electrical operating instructions Door control panel TS 956 Software 1 1 Design and functions subject to change 51171301 d 02 2013 en...

Страница 2: ...CH CONNECTION 9 Plug in system 9 Terminal version until year 1997 10 MAINS SUPPLY 11 MOTOR CONNECTION internal wiring 12 PHASE ROTATION 12 LIMIT SWITCH ADJUSTMENT 13 HARDWARE OVERVIEW 14 WIRING DIAGRA...

Страница 3: ...Key switch X5 18 Fully closed control 18 Potential free changeover contact X9 19 Maintenance cycle counter 19 Short circuit overload monitor 19 OPERATING STATUS DISPLAY 20 TECHNICAL DATA 21 LIFETIME D...

Страница 4: ...and gates Safety in use of power operated doors Requirements and left the factory in perfect condition from the point of view of safety To maintain this condition and to ensure safe operation the user...

Страница 5: ...with a permanent mains connection an all pole main switch with appropriate back up fuse must be provided Check live cables and conductors regularly for insulation faults or breakages When a fault is d...

Страница 6: ...Control page 8 LIMIT SWITCH CONNECTION Plug in system page 9 LIMIT SWITCH CONNECTION Terminal version until year 1997 page 9 Check Mains supply page 11 Check Phase rotation page 12 Adjustmemt Limit s...

Страница 7: ...sh button Emergency stop Connection cable ELEKTROMAT for Motor and mechanical limits NES 11 5 5 3 Spiral cable for pass door slack wire switch 2 Number of cores in the cable Important Using the connec...

Страница 8: ...end and for easy fitting The plugs for motor and control panel are different and cannot be interchanged Cable Description Motor plug to control Panel PIN Wire No 1 3 Phase W 2 2 Phase V 3 1 Phase U 4...

Страница 9: ...Page 9 LIMIT SWITCH CONNECTION Plug in system...

Страница 10: ...Page 10 LIMIT SWITCH CONNECTION Terminal version until year 1997 M 3...

Страница 11: ...1 Fig 2 Fig 3 Fig 5 Fig 4 asymmetric winding symmetric winding Important note The bridge must be fitted into the right terminal otherwise the print could be destroyed MAINS SUPPLY External fuse Contr...

Страница 12: ...h through electric shock Before changing phase rotation the mains supply must be switched OFF Three phase 3 x400 V AC N PE Star connection Three phase 3 x230 V AC PE Delta connection Single phase 1x23...

Страница 13: ...se position limits have been set the safety limits are automatically pre adjusted Eventually fine adjustment could be required Please see Mechanical Operating Instruction After reaching the final open...

Страница 14: ...0V V1 7 segment display 1 9 L1 fused with F1 1A MOT Motor connection 1 8 N NES Mechanical limit connection only with 3 x 400V N PE und 1 x 230V N PE Internal push button X2 Pass door plug X3 Emergency...

Страница 15: ...ation Key switch with stop button Close Stop Open Stop Open Close Key switch intermediate stop Aux contact Terminal box Bridge passdoor slack wire switch contact spiral cable Open Close or plug in bri...

Страница 16: ...til display 00 Press selector and 1 Enter programming Mode Press selector switch for 3 sec until display 00 2 Chose program and confirm Turn selector press selector 3 Adjustment Turn selector 4 Memori...

Страница 17: ...ctor The cycles would be displayed as follow M 1 000 000 H 100 HT 100 000 Z 10 ZT 10 000 E 1 T 1 000 2 Chose program and confirm Press selector OFF Relay function Switch contact impulse signal Switch...

Страница 18: ...TY DEVICES Mounting the spiral cable A bush is provided on both sides of the control box for mounting the spiral cable Push the plugs through into the enclosure until there is sufficient cable to allo...

Страница 19: ...ol TS 956 provides 230V AC for external devices 230V AC max 1A Maintenance cycle counter Free adjustable maintenance cycle counter Menu 8 5 makes it possible to pre adjust a max No of cycles until a m...

Страница 20: ...p activated Check the emergency stop is activated or whether the supply cable is broken Safety open or close limit operated Turn mains supply OFF and move the shutter downwards with the manual operato...

Страница 21: ...we recommend a replacement for control boards in use after doors having reached their confirmed lifetime cycles Coherence between power and amount of cycles for ELEKTROMATEN describes diagram bellow...

Страница 22: ...1A t External supply fuse 10A delayed Permitted Load ca 15 VA without motor and ext 230V External supply 1 230V via L1 and N safety fuse F1 1A t Inputs 24V DC typ 10mA signal length must be more than...

Страница 23: ...ant technical documents internal EU address Dipl Ing Bernd Synowsky Documentation representative Incomplete machines within the meaning of the EC Directive 2006 42 EC shall only be intended to be inte...

Страница 24: ...n open and close Self hold open and dead man mode close Fully closed control Supply for external devices 230V at 400V 3 with N up to 1A load Plug connection for the motor 5 pole and limit switches 6 p...

Отзывы: