Page 11
The CONTROL PANEL TS 956 has a universal electric supply and works with the following
supplies. (See diagram Fig.1-5)
DANGER! To the life and health thru electric shock.
Before mounting the mains supply must be switched OFF.
The supply disconnect device (Main switch or CEE plug) must be installed between 0,6m
and 1,7m above floor level.
Mains supply terminal
Fig.: 1
Fig.: 2
Fig.: 3
Fig.: 5
Fig.: 4
asymmetric winding
symmetric winding
Important note!
The bridge must be fitted into the right terminal otherwise the print could be
destroyed.
MAINS SUPPLY
External fuse!
Control must be saved against short circuit and overload by an external fuse,
max. 10A delayed, in the mains supply. An automatic cut off switch is required,
regarding the supply for three-phase or single-phase.
When connecting control to mains supply a mains isolator switch or (16A CEE – plug) according
EN 12453 is required.
400V – mains supply = 1.5 / 1.6
230V – mains supply = 1.6 / 1.7