Check the door position:
Close the door ① until the cam is released
and open it again ② until the OPEN final limit
position is reached.
The OPEN final limit position can be
corrected by following the fine adjustment
procedure. Check the door position after each
correction.
The S1 EMERGENCY OPEN limit switch is preset by the setting of the OPEN final limit
position. The door must stop without posing any risks should the rotating direction be
incorrect or should there be a fault with the S3 OPEN limit switch. Follow the fine adjustment
procedure to correct the switching point of the limit switch as needed.
Setting of CLOSE final limit position and auxiliary limit switch
The same setting procedure applies as for setting the OPEN final limit position.