2551 & 2552 Operation

Notes:

Averaging

Set the time the Magmeter will use as the averaging period. 
Example:  With averaging at 14 seconds, each display is an average of the previous 

 

14 seconds input. Use higher averaging times to smooth the display and current output 

 

where the flow in the pipe is erratic.

Sensitivity

Set the percentage of change in the flow rate required to allow the Magmeter to override AVERAGING 

and jump to a new flow rate immediately (2551 maximum range is 10 m/s).
See Magmeter manual for an explanation of Averaging and Sensitivity:  

www.gfps.com

Noise Rejection

Select 50 Hz or 60 Hz according to local AC power specifications.

Low Flow Cut Off

Set the flow rate where all Magmeter outputs will be forced to zero.
When the flow rate is at or below this value, the frequency output will be 0 Hz and the 

 

current output will be 4 mA.

1

2
3
4
5
6
7
8

9

10

11 & 12

13a

13b

(General Software Operation, pg. 7)

9

GF 0252 Configuration Tool

Содержание Signet 0252

Страница 1: ...ngs to factory default condition Calibrate 258X FlowtraMag Full Bore Magmeter 2610 Dissolved Oxygen Sensor and pH ORP sensors using the 2751 Smart Sensor Electronics Microsoft and Windows are register...

Страница 2: ...Blue Indicator DATA COMMUNICATION Input connections 3 terminal connectors max 14 AWG Electrical Communication rate Maximum 19 2 kbs Input power Supplied by USB interface Output power 5 VDC 5 Power con...

Страница 3: ...the drop down menu Supported languages English French German Spanish Italian Portuguese Chinese 5 Click Save to set language preference Caution Managed systems and network systems may have security m...

Страница 4: ...ndows PC Black Red White 1 2 3 4 White Red Black S USB GND Data 5V out USB GND Data 5V out Windows PC Windows PC Black Red White 1 2 3 4 White Red Black S USB GND Data 5V out USB GND Data 5V out Windo...

Страница 5: ...ire 1 Additional wire required Brown Black White Blue White Blue Wire Nut To VDC To GND Wire 3 Wire 2 USB GND Data 5V out Windows PC Brown Black White Blue USB GND Data 5V out Windows PC Isolated 24 V...

Страница 6: ...ower Supply 12 to 32 VDC Brown Blue Green No connection CAUTION Do not connect power directly to the 0252 Configuration Tool Improper power supply wiring can cause damage to the 0252 hardware and comp...

Страница 7: ...reset the connected device to a factory default condition NOTE Performing the above reset to factory default condition will not change the input type on the 9900 Transmitter NOTE Certain sensors 2250...

Страница 8: ...ut Off of full scale 0 0 to 20 Full Scale Loop Output settings 11 4 mA Set Point Flow Units Time Base 0 00000 0 00000 999999 00000 12 20 mA Set Point Flow Units Time Base 5 00000 Write or Save setting...

Страница 9: ...allow the Magmeter to override AVERAGING and jump to a new flow rate immediately 2551 maximum range is 10 m s See Magmeter manual for an explanation of Averaging and Sensitivity www gfps com Noise Rej...

Страница 10: ...Select Output modes 4 to 20 mA as either Active or Passive S L or Frequency output Note Setting the 258X to frequency will prevent the use of the 0252 tool You will need to change the 258X back to S...

Страница 11: ...258X Operation 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 11 GF 0252 Configuration Tool...

Страница 12: ...low Rate settings 6 Wait for flow reading to stabilize then enter correct flow and Click Set Flow 7 Cancel Flow Rate Calibration and return to Calibration screen Volumetric settings 8 Start Volumetric...

Страница 13: ...258X Calibration 6 7 8 9 10 11 13 GF 0252 Configuration Tool...

Страница 14: ...Water Salinity Value for Salt Compensation 0 Fresh Water Loop Output settings 5 Select Measurement Dissolved Oxygen or Temperature for 4 to 20 mA Output 6 Set 4 mA Set Point 7 Set 20 mA Set Point Inf...

Страница 15: ...ated Water click Start to begin the Calibration 4 Once probe reading is stable click Continue Second Point settings 5 With probe in 0 Saturated Water click Start to begin the second point Calibration...

Страница 16: ...ss Impedance Set Point for Alarm pH 10 Glass Impedance Update Timer pH Information settings 11 Click Get Data to Update Sensor Data 12 Electrode Serial Number pH or ORP 13 Electrode Part Number pH or...

Страница 17: ...2751 Operation 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 17 GF 0252 Configuration Tool...

Страница 18: ...Click Next for two point calibration 9 Click End to complete one point calibration 10 To cancel calibration click Cancel and return to Calibration Screen Temperature Calibration settings 11 Start Cali...

Страница 19: ...2751 Calibration 5 6 7 8 9 10 11 12 19 GF 0252 Configuration Tool...

Страница 20: ...2751 Calibration 13 14 15 16 17 20 GF 0252 Configuration Tool...

Страница 21: ...on settings 3 Select the Input Calibration Loop Relay or Option tabs to choose the desired menu for the selected sensor 4 Refer to the 9900 manual for details pertaining to specific settings for each...

Страница 22: ...9900 Operation 2 3 5a 5b General Software Operation pg 7 22 GF 0252 Configuration Tool...

Страница 23: ...the maximum interval is 86400 seconds 24 hours Example If the Log Interval is set to 60 seconds the 0252 will record the temperature once every minute 4 The 0252 saves data files in csv format The ma...

Страница 24: ...ce visit our website www gfps com Or call in the U S 800 854 4090 For the most up to date information please refer to our website at www gfps com 3 0252 090 Rev 3 01 22 English Georg Fischer Signet LL...

Отзывы: