Mixed water temperature 

constantly too low

Mixed water temperature 

constantly too high

Installation instructions/schematic 

diagram disregarded,

or pressure rates of cold and hot water 

differ

Water heater not at target temperature

JRGUMAT installed above or too close to 

the water heater

Circulation connection on the JRGUMAT 

not flat sealing or not properly connected 

flat sealing

Too low/high volume flow through the 

JRGUMAT

Slide in JRGUMAT stuck due to dirt/

deposits

Too low/high volume flow through the 

JRGUMAT

Installation instructions/schematic 

diagram disregarded,

or pressure rates of cold and hot water 

differ

Slide in JRGUMAT stuck due to dirt/

deposits

Adjust installation according to instructions 

in the manual; if not possible: install pressu-

re reducers in the cold and hot water pipes 

upstream before the JRGUMAT

Check water heater, increase hot water 

temperature if necessary

Install the JRGUMAT side by side with the wa-

ter heater or install thermosiphon in the hot 

water pipe upstream before the JRGUMAT

Use flat sealing union or cap

Check dimension of JRGUMAT; choose 

smaller/larger dimension if necessary

Replace JRGUMAT

Check dimension of JRGUMAT; choose 

smaller/larger dimension if necessary

Adjust installation according to instructions 

in the manual; if not possible: install pressu-

re reducers in the cold and hot water pipes 

upstream before the JRGUMAT

Replace JRGUMAT

Maximum differential pressure of hot and cold 

water: ~0.5 bar

Hot water temperature must be 5 K higher 

than the desired mixed water temperature

Install the JRGUMAT side by side with the water 

heater with a 1 metre clearance; if clearance 

<1 m: install thermosiphon in the hot water pipe

Adhere to installation instructions

Use nomogram to determine the appropriate 

dimension of the JRGUMAT securing a volume 

flow of ±1 K target value range

Install water treatment components (filter 

and/or softener)

Use nomogram to determine the appropriate 

dimension of the JRGUMAT securing a volume 

flow of ±1 K target value range

Maximum differential pressure of hot and cold 

water: 0.5 bar

Install water treatment components (filter 

and/or softener)

!

 

Malfunction

?

 Possible cause

 Possible action

 

Precaution

JRGUMAT  –  Trouble  shooting               

 

 

                                               

1/2

General

Blocked shut-off valves and damaged 

back flow preventer

Check functionality of valves, replace back 

flow preventer

Regular control and maintenance of all valves

37 201 62 / e / 05.17