TSA 160 NT
25
Configurable inputs
11.8 Operating mode switchover Off
à
The configurable inputs can be used to change between the operating mode Off as required (depending on
the parameter setting). This can, for example, be advisable if the mode of operation is switched by a timer via
the available programme switching inputs (AU, DO).
à
The operating mode change is not possible if the analogue programme switch MPS is connected since this specifies
the operating modes Off in a fixed form.
à
Setting the parameters:
à
DPS: Set
e1
or
e2
to
0 2
(Off , normally opened contact NO) or
2 6
(OFF, normally closed contact NC).
à
ST220: Set “PE1 function” or “PE2 function” to “Off normally opened contact NO” or “OFF normally closed contact NC”.
à
S1, S2: Set parameter 17 or 18 to value 02 (Off normally opened contact NO) or 26 (OFF normally closed contact NC).
51 PE1
2 24V
PE1
52 PE2
PE2
or
11.9 STOP
The configurable inputs PE1 and PE2 can be used for connection of a stop push button or sensor strip. Input PE2
is also suitable for analogue evaluation.
à
On activation, the door leaf stops (in case of 2-leaf systems both leaves) and remains at a standstill as long as
the input is active.
à
In the case of 2-leaf systems the stop push button can be connected to the active leaf control or to the passive
leaf control.
For PE1, PE2:
à
Set the parameter contact type with:
à
DPS: Set
e1
or
e2
to
1 5
(Stop normally opened contact) or
1 6
(Stop normally closed contact).
à
ST220: Set “Signals”, “Input signals”, “PE1 function”, “PE2 function” to “Stop normally opened contact NO”
or “Stop normally closed contact NC”.
à
S1, S2: Set parameter 17 or 18 to the value 15 (Stop normally opened contact) or 16 (Stop normally closed contact).
or
E1 = 16
E1 = 15
E2 = 16
E2 = 15
For PE2:
à
In order to ensure protection of persons as specified in DIN 18650 / EN 16005, a terminating resistor 1.2 kΩ or 2.0 kΩ
must be connected to monitor the input. The terminating resistor must be connected directly to the switch contact.
à
Set the parameter “Contact type” with:
à
DPS:
e2
to
1 2
(Stop 1.2k) or 20 (Stop 2.0k)
à
ST220: Set “Signals”, “Input signals”, “PE2”, “PE2 function” to “Stop 1.2 kOhm” or “Stop 2.0 kOhm”.
à
S1, S2: Set parameter 18 to 12 (Stop 1.2 kOhm) or 20 (Stop 2.0 kOhm).
Value 12, terminating with
1.2 kΩ
Value 20, terminating with
2.0 kΩ