Safety instructions for the operator and the user
Intended use
The RWA system is used to ventilate and, in the event of a fire, automatically extract
smoke from rooms.
Your RWA-Emergency Power Control System is a state of the art system and
complies with the valid safety regulations. GEZE shall not be responsible for damage
resulting from changes made to the RWA-Emergency Power Control System arbit-
rarily.
Obligations of the user
As the user, you must ensure that the person operating the RWA-Emergency Power
Control System has been instructed in the operation of the system as described in
Chapter 1 of this manual. Please ensure that the key for the RWA switch can only be
accessed by authorised persons.
Check the display of the RWA-Emergency Power Control System on a regular basis
- at least every 4 days. In the event of a fault, read Section 1.6, What to do when …?
In the event of a fire
The emergency functions of the RWA-Emergency Power Control System can be
triggered in the event of a fire from a smoke extractor.
Instruction
The client or the owner-operator has to be instructed in proper use of the RWA system
during commissioning or handing over.
The client or the owner-operator has to confirm in writing that the instruction has been
carried out.
Maintenance
As needed - but at least once a year - you must have a specialist approved by GEZE
inspect the system and perform any necessary maintenance. You will receive a
written report regarding the inspection. The two batteries must be replaced after no
more than 4 years.
Please keep this manual and the connection diagram where it can be easily
accessed.
To reset a fire alarm, the RWA-Emergency Power Control System may only be
operated by an operator who has read Chapter 1, Operation in this manual. In
particular, the safety instructions in Section 1.4, Fire alarm must be complied
with.