FUNCTIONS
The switching actuator wilh manual actuation is for switching lamps and other
users via make contacts. The device is equipped with twelve independent
channels (A to L) with floating relay outputs and an integrated Bus coupler.
The function of the channels is determined by the loaded user software.
Display and operating elements
1 green LED:
operating LED lights up when the applicati-on has been
loaded correctly.
1 red LED:
programming control
1 button:
programming
12 hand switches: for manual operation of the switching contacts (A to L),
even in the absence of Bus voltage.
INSTALLATION
WARNING:
Adjacent devices may get damaged! Only install devices
with at least a basic insulation next to the switching actuator.
1
Place the device into the DIN rail from below and push upwards. The push
the top of the device against the rail and hook it in. No data rail is required.
WARNING:
Switching actuator may get damaged. Protect switching
contacts with upstream 16 A circuit breakers.
2
Connect the device as shown in the example. The cables to the users and
the mains voltages (L1, L2 or L3) are connected via screw terminals for a
maximum of 16 A. Each pair of L connections is connected internally.
3
Plug in Bus supply terminal and cable cover.
WARNING:
A safety gap in accordance with DIN VDE 0110. Section 1
must be ensured.Ensure that there is a gap of at least 4 mm be-
tween the individual wires of the 230 V line and the Bus line.
STARTING UP THE DEVICE
After wiring the device, the physical address is allocated and the parameters
are set:
1
Connect interface to Bus
2
Switch on Bus voltage
3
Press the programming key (red LED lights up)
4
Loading of physical address from the ETS via interface (red LED goes out)
5
Loading of prepared parameterisation into the device via interface (green
LED lights up)
6
Test chosen function when device is operational (also possible with the aid
of the ETS)
TECHNICAL DATA
External auxiliary voltage:
none
Supply from Bus:
DC 24 V / approx. 15 mA
Insulation voltage:
AC 4 kV between Bus and 230 V AC
SWITCHING CONTACTS A TO L:
12 x make contacts, floating
Protection:
Protect the switching contacts with upstream 16 A circuit breaker
Nominal voltage:
AC 230 V, 50 to 60 Hz
Nominal current:
16 A, cos
ϕ
= 0,6
Connected load:
- Incandescent lamps: AC 230 V, max. 3600 W with 10,000 switching cycles
- Halogen lamps: AC 230 V, max. 2500 W with 10,000 switching cycles
- Fluorescent lamps: AC 230 V, max 2500 VA, parallel-compensated, with
5,000 switching cycles
- Capacitive load: AC 230 V, 16 A max. 200
µ
F with 5,000 switching cycles
Minimal loads:
≥
24 V DC, 100 mA
Switching frequency:
max. 10 per minute at nominal load
Ambient temperature:
- Operation: -5°C to +45°C
- Storage: -25°C to +55°C
- Transport: -25°C to +70°C
Surroundings:
The device is designed for use at an altitude of up to 2000 m
above sea level.
Max. humidity:
93%, no moisture condensation
Control elements:
Programming key, eight hand switches for manual operation
Display elements:
- Programming control: 1 red LED
- Readiness of operation: 1 green LED
Connections:
- Bus: via two 1 mm pins for Bus supply terminal
- Outer conductor: eleven 3-gang screw terminals (A - K) and one 2-gang
screw terminal (L) for max. 2.5 mm
2
Device width:
12HP = approx. 216 mm
EC guidelines:
complies with low-voltage - guideline 73/23/EWG, complies
with EMC guideline 89/336/EEC
Connection illustrator:
BINARY OUTPUT 12 CHANNELS 16A
B
L
T
+ --
ON
Bus
Prog.
L
L
L
L
L
L
L
L
L
L
L
L
L
K
OFF
L
OFF
RUN
OFF
OFF
OFF
OFF
OFF
J
I
H
G
F
E
1000W
AC 230V
16AX
OFF
OFF
OFF
OFF
D
C
B
A
L
L
L
L
L
L
L
L
L
Article no.
GW 90 738
Cod. 7.00.8.969.3
GB
230V
Bus
Bus
+39 035 946 111
8.30 - 12.30 / 14.00 - 18.00
for monday to friday
+39 035 946 260
24 hours/day
SAT on line
[email protected]
@
SAT
GEWISS - MATERIALE ELETTRICO