FUNCTIONS 

The switching actuator wilh manual actuation is for switching lamps and other
users via make contacts. The device is equipped with twelve independent
channels (A to L) with floating relay outputs and an integrated Bus coupler.
The function of the channels is determined by the loaded user software.

Display and operating elements

1 green LED: 

operating LED lights up when the applicati-on has been
loaded correctly.

1 red LED:

programming control

1 button:

programming

12 hand switches: for manual operation of the switching contacts (A to L),

even in the absence of Bus voltage.

INSTALLATION

WARNING:

Adjacent devices may get damaged! Only install devices

with at least a basic insulation next to the switching actuator.

1

Place the device into the DIN rail from below and push upwards. The push
the top of the device against the rail and hook it in. No data rail is required.

WARNING:

Switching actuator may get damaged. Protect switching

contacts with upstream 16 A circuit breakers.

2

Connect the device as shown in the example. The cables to the users and
the mains voltages (L1, L2 or L3) are connected via screw terminals for a
maximum of 16 A. Each pair of L connections is connected internally.

3

Plug in Bus supply terminal and cable cover.

WARNING:

A safety gap in accordance with DIN VDE 0110. Section 1

must be ensured.Ensure that there is a gap of at least 4 mm be-
tween the individual wires of the 230 V line and the Bus line.

STARTING UP THE DEVICE

After wiring the device, the physical address is allocated and the parameters
are set:

1

Connect interface to Bus

2

Switch on Bus voltage

3

Press the programming key (red LED lights up)

4

Loading of physical address from the ETS via interface (red LED goes out)

5

Loading of prepared parameterisation into the device via interface (green
LED lights up)

6

Test chosen function when device is operational (also possible with the aid
of the ETS) 

TECHNICAL DATA

External auxiliary voltage:

none

Supply from Bus:

DC 24 V / approx. 15 mA

Insulation voltage:

AC 4 kV between Bus and 230 V AC

SWITCHING CONTACTS A TO L:

12 x make contacts, floating

Protection:

Protect the switching contacts with upstream 16 A circuit breaker

Nominal voltage:

AC 230 V, 50 to 60 Hz

Nominal current:

16 A, cos 

ϕ

= 0,6

Connected load:

- Incandescent lamps: AC 230 V, max. 3600 W with 10,000 switching cycles
- Halogen lamps: AC 230 V, max. 2500 W with 10,000 switching cycles
- Fluorescent lamps: AC 230 V, max 2500 VA, parallel-compensated, with

5,000 switching cycles

- Capacitive load: AC 230 V, 16 A max. 200 

µ

F with 5,000 switching cycles

Minimal loads:

24 V DC, 100 mA

Switching frequency:

max. 10 per minute at nominal load

Ambient temperature:

- Operation:  -5°C to +45°C
- Storage: -25°C to +55°C
- Transport:  -25°C to +70°C

Surroundings:

The device is designed for use at an altitude of up to 2000 m

above sea level.

Max. humidity:

93%, no moisture condensation

Control elements:

Programming key, eight hand switches for manual operation

Display elements:

- Programming control: 1 red LED
- Readiness of operation: 1 green LED 

Connections:

- Bus: via two 1 mm pins for Bus supply terminal 
- Outer conductor: eleven 3-gang screw terminals (A - K) and one 2-gang

screw terminal (L) for max. 2.5 mm

2

Device width: 

12HP = approx. 216 mm

EC guidelines:

complies with low-voltage - guideline 73/23/EWG, complies

with EMC guideline 89/336/EEC

Connection illustrator:

BINARY OUTPUT 12 CHANNELS 16A

B

L

T

+ --

ON

Bus

Prog.

L

L

L

L

L

L

L

L

L

L

L

L

L

K

OFF

L

OFF

RUN

OFF

OFF

OFF

OFF

OFF

J

I

H

G

F

E

1000W

AC 230V

16AX

OFF

OFF

OFF

OFF

D

C

B

A

L

L

L

L

L

L

L

L

L

Article no.

GW 90 738

Cod. 7.00.8.969.3

GB

230V

Bus

Bus

+39 035 946 111

8.30 - 12.30 / 14.00 - 18.00

for monday to friday

+39 035 946 260

24 hours/day

SAT on line