65
6 -
T
ECHNICAL DATA TABLE
OPERATION POWERED BY
OVERLOAD TIMES
BYPASS
INVERTER
100% < Load
≤
110%
Activates bypass after 2 sec
Stoppage after 120 sec
Stoppage after 60 sec
110% < Load
≤
150%
Activates bypass after 2 sec
Stoppage after 4 sec
Stoppage after 4 sec
Load > 150%
Activates bypass instantaneously
Stoppage after 1 sec
Stoppage after 0.5 sec
(1)
@ nominal load, minimum voltage of 164 Vac, battery charging
(2)
@ nominal load, nominal voltage of 230 Vac, battery charging
(3)
Mains/Battery @ load 0% -100%
(4)
@ Mains/battery/mains @ resistive load 0% / 100% / 0%
(5)
If the mains frequency is within ± 5% of the value selected, the UPS is synchronized with the mains. If the
frequency is outside the tolerances or operation is battery-powered, the frequency is the selected fre0.1%
(6)
20 - 25 °C for longer battery life
(7)
To maintain the output voltage inside the precision range indicated, a recalibration may be necessary after a long
period in operation