19
TRS 5-52 - Installation & Operating Manual -
819175-05
Action against high-frequency interference
High-frequency interference can be caused by out-of-phase switching operations. If such interference
occurs and results in sporadic failure, we recommend taking the following action to suppress interference:
n
Provide inductive loads with RC combinations as per manufacturer's specifications.
n
Route the connecting cable to the temperature sensor separately from power lines.
n
Increase the distance from sources of interference.
n
Check the shield connection on the temperature sensor.
n
Suppress HF interference using hinged-shell ferrite rings.
Further information
Replacing/taking the equipment out of service
Disposal
The equipment must be disposed of in accordance with statutory waste disposal regulations.
The upper terminal strip of the equipment is live during operation.
There is a risk of serious injury due to electric shock!
Always
cut off power
to the equipment before working on the terminal strip (installation,
removal, connecting cables).
Danger
n
Switch off the supply voltage and
cut off power to the equipment.
n
Remove the upper and lower terminal strips.
Fig. 6
n
Insert a screwdriver on the right and left between the terminal strip and the front frame,
as shown by the arrows.
n
Release the terminal strip on the right and left sides, by turning the screwdriver in the direction of
the arrow.
n
Remove the terminal strips.
Fig. 6
n
Release the white slider holder on the underside of the housing and remove the equipment from
the support rail.
5
6
7
8
1
2
3
4
1
ON
2 3 4
In the event of malfunctions or faults that cannot be remedied with the aid of this Installation & Operat-
ing Manual, please contact our service centre or authorised agent in your country.