Pressure & temperature ratings
The following pressure, temperature and pH limits
refer to equipment without sightglass. For
information on limiting conditions for the individual
components refer to the respective installation &
operating manuals.
The lowest or highest limit of any component
determines the decisive overall limiting conditions of
the equipment.
Limiting conditions for steel version QuickEM PN16/QuickEM-Control PN16
pH value
≤ 9
Pressure p
[barg]
16.0
14.4
12.8
11.2
9.6
Temperature T
[°C]
–10/20
100
200
250
1
280
1
1
If QuickEM Control together with measuring electrode NRG 16-27 or NRG 16-28 is used, the max.
admissible temperature limit is 238 °C.
Limiting conditions for steel version QuickEM PN40/QuickEM-Control PN40
pH value
≤ 10
Pressure p
[barg]
40.0
37,1
33,3
30,4
27,6
Temperature T
[°C]
–10/20
100
200
250
1
300
1
1
If QuickEM Control together with measuring electrode NRG 16-27 or NRG 16-28 is used, the max.
admissible temperature limit is 238 °C.
Limiting conditions for stainless steel version QuickEM PN16/QuickEM Control PN16
pH value
≤ 7
1
Pressure p
[barg]
16.0
12.5
10.0
9.0
9.0
Temperature T
[°C]
–10/20
100
200
250
2
280
2
1
Fluids with pH value above 7 have the potential to cause glass corrosion. As the temperature and pH
value of the fluid increases, the possibility of etching the glass also increases.
2
If QuickEM Control together with measuring electrode NRG 16-27 or NRG 16-28 is used, the max.
admissible temperature limit is 238 °C.