21
PRS 50 - Installation & Operating Manual -
850652-00
PRS 50
S/B
!
Bringing into service – starting, operation and testing
The operating panel and signal LEDs
Fig. 7
7-segment display
Standby/burner LED (yellow)
Valve LED
(yellow)
Alarm LED (red)
Rotary knob with integrated
push-button
■
Before bringing into service, check that the PRS 50 blowdown timer and all equipment
is correctly connected.
■
Next, switch on the supply voltage.
Starting
Switch on the
supply voltage
The display is on and the LEDs
light up briefly.
Display:
S-xx = software version
t-02 = equipment type PRS 50
System test, takes approx. 3 seconds
Valve output contact 17/18 open.
Alarm output contact 19/20 open.
Countdown of two-minute
remaining runtime until inter-
mittent blowdown after startup.
Configuration:
Standby function.
No input active.
Display:
Remaining runtime = mm.ss
Valve output contact 17/18 open.
Alarm output contact 19/20 closed.
The remaining runtime
has elapsed. Blowdown after
startup is initiated.
Display:
Remaining runtime until next
intermittent blowdown.
Valve LED
= On
Valve output contact 17/18 closed.
Alarm output contact 19/20 closed.