Operational malfunctions
Fault finding list for troubleshooting
Level electrode exposed - High-level alarm
Fault:
The level switch raises a high-level alarm before the level in the boiler has reached
the high-level mark.
Remedy:
Check length of high-level electrode tip. Make sure that the level switch and the
electrode are wired in accordance with the wiring diagram.
Fault:
After lowering the water level below the high-level mark, the two red LEDs
0
are
still illuminated or go out only after quite some time.
Remedy:
Check whether the protection tube is provided with a vent hole.
If the electrode is fitted in a measuring pot outside the boiler, check positions
of isolating valves.
Fault:
One or both LEDs
0
light up without the water level having reached the high-level
mark.
Remedy:
This means loss of redundancy in the level switch, i. e. failure of one or two of the
channels. Replace level switch.
High water level reached - no function
Fault:
The water level exceeds the high-level mark but neither of the two red LEDs
0
lights up.
Remedy:
Check whether the protection tube is provided with a vent hole.
If the electrode is fitted in a measuring pot outside the boiler, check positions
of isolating valves. Measure the conductivity of the boiler water and compare the
value obtained with the specification on the name plate.
Fault:
The test “TEST 2 / INSPECTION”
9
was not successful, i. e. only one red LED
0
or
none of the two lit up after max. two minutes .
Remedy:
Replace level switch.
Operation
Use in conjunction with level switch NRG 1...-12 in steam and pressurised hot water plants in accord-
ance with TRD 401, TRD 602, TRD 604, EN 12952, EN 12953 or according to other national regulations.
Water level limiter
Notice
n
To analyse and eliminate malfunctions refer to section
“Fault finding list for troubleshooting” on pages 17 – 18.
Содержание NRS 1-8
Страница 1: ...1 NRS 1 8 Installation Instructions 818612 03 Level Switch NRS 1 8 GESTRA Steam Systems EN English ...
Страница 8: ...8 Technical Data continued Dimensions Fig 2 106 7 32 51 Fig 3 112 85 ...
Страница 9: ...9 Component Parts 7 2 3 6 5 4 Fig 4 Fig 5 Fig 6 1 NRS 1 8 1 ...
Страница 10: ...10 Fig 7 b 9 0 a MAX 55 C MAX 95 IP 65 Functional Elements NRS 1 8 ...
Страница 13: ...13 Installation continued Fig 8 4 2 5 8 6 6 3 1 Fig 9 7 7 MAX 55 C MAX 95 IP 65 Examples of installation ...