Wiring

Wiring should be carried out in accordance with
wiring diagram (Fig. 3).

For wiring to the electrode, screened cable,
e. g.  4 x 0.5 mm

2

 is recommended, maximum

cable length 100 m.

Design

Plug-in unit in plastic case for installation in
control cabinets. The terminals in the case are
accessible after loosening two screws and un-
plugging the unit from its base. To avoid con-
fusion with other plug-in units of the GESTRA
range, inserts are fitted in the bases so that
only the correct unit may be plugged into each
base.

The plug-in units may be snapped onto a 35
mm supporting rail or screwed into position on
a mounting panel.

Field enclusures for several plug-in units are
available on request.

Installation of Level Controller

On supporting rail 

(with mounting clip)

1. Snap level controller onto supporting rail.

2. Loosen cover screws      and unplug

cover       from its base       (see Fig. 1).

3. Select cable entry      and remove cor-

responding seal.

On mounting panel

1. Loosen cover screws      and unplug

cover       from its base       (see Fig. 1).

2. Unscrew mounting clip      .

3. Drill the hole      marked in the base to

4.3 mm dia.

4. Fasten base with two M4 screws onto

mounting panel.

5. Select cable entry      and remove cor-

responding seal.

No user serviceable parts are containes within
the equipment. All repairs must be performed
only by the manufacturer. Misuse or any at-
tempted modification of the equipment will lead
to considerable safety risks!

Important Safety Notes

Technical Data

Input

Four connections for 3 electrode tips.

Output

One volt-free working contact for the controller,
one volt-free relay contact for the alarm;
max. contact rating: 250 V, 500 W, 3 A resistive
with a life of 4 x 10

5

 switching cycles or 0.35 A

inductive with a life of 2 x 10

6

 cycles;

contact material silver, hard-gold plated.

Sensitivity

Standard design: 10 µS/cm
Special design: 0,5 µS/cm

Electrode supply voltage

11 V AC, free from DC voltage

Indicators and adjustors

ONE LED “Pump ON”, 1 LED “MAX/HW”,
one switch for selection of operation “Feed” or
“Drain” control,
one “Test” button for simulating “high-level
alarm” (HW)

Mains supply

24 V, 110 V, 120 V, 220 V, 240 V, 50 . . . 100 Hz,
3,5 VA,
24 V DC supply also possible with the ancillary
unit type URN-1.

Protection

IP 40

Permissible ambient temperature

0 . . . 50 °C

Case materials

Base: ABS plastic, black
Cover: polystyrene (highly shock-resistant),
stone grey

Approx. weight

0.8 kg

Dimensions

See Fig. 1.

Connect screen only to terminal 12 of the
level controller, but not at the electrode.

The screen must not make any other elec-
trical contact.

The mains voltage is indicated on the name
plate.

Important Notes

Purpose

On-off feedwater control and high-level alarm
for use in conjunction with the GESTRA mul-
tiple level-control electrode type 

ER 5 . . .

 or

level control electrodes type 

ER 16

.

Performance Tests

1. Ensure that electrode tips are completely

exposed from the water surface.

2. Set switch      on position “Feed pump”.

3. The LED “Pump ON”      must light up.

4. When switching to “Drain Pump”, the LED

“Pump ON”       must extinguish.

5. Fill vessel with water up to the high-level

mark.

6. With the switch in position “Feed pump”,

the LED “MAX/HW”      must light up.

7. With the switch in position “Drain pump”,

the LED “Pump ON”      must light up.

8. The operation of the level controller can

be checked with the aid of the button “Test
HW”      .

After pushing this button, the LED “MAX/
HW”      must light up.

With the aid of the Electrode Simulation Set
ER 5-S the performance test of the level
controller is made easier.

Fault Finding

Fault A:

 The level controller signals MAX/HW

alarm before the level in the vessel has reached
the high-level mark

.

Remedy:

 Check length of electrode tips. Check

correct wiring of level controller and electrodes
in accordance with wiring diagram, Fig. 3.

Fault B:

 The LED “MAX/HW” does not light up,

although the switch is in position “Feed pump”
and the electrodes are completely submerged.

Remedy:

 Check correct wiring of level controller

and electrodes in accordance with wiring dia-
gram, Fig. 3.

If the electrode is installed in a boiler external
level pot, check position of isolating valves.

Fault C:

 The LED “MAX/HW” does not light up

although the electrodes are completely sub-
merged.

The feed pump is not switched off. The drain
pump is not switched on.

Remedy:

 Determine the conductivity of the

liquid to be monitored. The minimum conduc-
tivity required is 

10 µS/cm

 for the standard

design and 

0.5 µS/cm

 for the special design

(see name plate).

Check whether electrode has been sealed off
with Teflon tape, if so, remove tape and use the
ring joint supplied with electrode.

Clean electrode tips.

It fault occur that are not listed above
please contact our subsidiary or agency in
your country.

Before unplugging the level controller NRS
1-5b, cut off power supply to base.

When replacing level-control electrode
check switchpoint of level controller.

When switching of inductive loads, voltage
spikes are produced that may impair the
operation of control and measuring systems.
We therefore recommend that inductive
loads are provided with commercial arc
suppressor RC combinations, e.g. 0.1 µF/
100 

Ω

.

Important Notes

B

A

C

B

A

D

C

D

F

E

1

1

2

3

3

4

1

Содержание NRS 1-5b

Страница 1: ...iveauschalter NRS 1 5b Installation and Service Instructions 808230 01 Level Controller NRS 1 5b Instructions de montage et de mise en service 808230 01 Commutateur amplificateur NRS 1 5b Instrucciones de montaje y servicio 808230 01 Amplificador de maniobra NRS 1 5b ...

Страница 2: ...HA Zulauf Ablauf Feed pump Drain pump Remplissage Vidange Entrada Salida MAX HW MAX HW NH MAX NA Test HW Test HW Test NH Test NA Alarm HW Alarm HW Alarme NH Alarma NA Netz Mains Secteur Red HW HW NH NA Pumpe Pump Pompe Bomba Pumpe Pump Pompe Bomba Abgebildete Kontaktstellung stromlos bzw Hochwasser überschritten Illustrated position of contacts relays deenergized i e alarm Contacts représentés en ...

Страница 3: ...g mit dem Schutzleiterpotential haben Die Nennspannung ist auf dem Typenschild angegeben Bitte beachten Sie Aufgabe Der Niveauschalter NRS 1 5 ist in Verbindung mit der Niveauelektrode ER 5 oder ER 16 ein Intervall Wasserstandregler mit Überfüll Alarm Funktionsprüfung 1 Die Elektroden müssen vollständig aus getaucht sein 2 Kippschalter auf Stellung ZULAUF schalten Fig 2 3 Die LED PUMPE EIN muß auf...

Страница 4: ...at the electrode The screen must not make any other elec trical contact The mains voltage is indicated on the name plate Important Notes Purpose On off feedwater control and high level alarm for use in conjunction with the GESTRA mul tiple level control electrode type ER 5 or level control electrodes type ER 16 Performance Tests 1 Ensure that electrode tips are completely exposed from the water su...

Страница 5: ...age avec le potentiel de protection terre doit être évité La tension du secteur est indiquée sur la plaque d identification Avis importants Application Régulateur de niveau entre deux points avec alarme niveau haut en combinaison avec l électrode de niveau multiple GESTRA type ER 5 ou les électrodes type ER 16 Contrôle du fonctionnement 1 Assurer que les électrodes sont complè ment émergées 2 Manœ...

Страница 6: ...biar sustituir el electrodo de nivel controlar de nuevo el punto de contacto del amplificador de maniobra Al desconectar consumidores inductivos se producen picos de tensión que perjudican el funcionamiento de instalaciones de mando y regulación Por ello se recomienda conectar los consumidores inductivos con combinaciones RC comerciales por ejem plo 0 1 µF 100 Ω Advertencias Construcción Caja ench...

Страница 7: ......

Страница 8: ...808230 01 1002c 1992 GESTRA AG Bremen Printed in Germany GESTRA AG Münchener Straße 77 28215 Bremen Germany Telefon 49 421 3503 0 Telefax 49 421 3503 393 E mail info de gestra com Web www gestra de ...

Отзывы: