27
NRS 1-50 For TWO electrodes - USA - Installation & Operating Manual -
850694-00
Operation
Action
Indication
Function
Level electrode(s)
immersed
Green level
electrode LED 1 / 2 lit
Output contacts closed,
signal outputs 1 / 2 open.
Alarm
Level electrode(s)
exposed, water is
below low water (LW)
level
Red level
electrode LED 1 / 2 flashing
Off delay in progress,
signal outputs 1 / 2 close without a delay.
Red level
electrode LED 1 / 2 lit
Delay has elapsed,
output contacts open.
Signal outputs 1 / 2 closed.
Test of channels 1 and 2
In operating mode:
Press button 1 or 2
and hold until the end
of the test. The level
switch must behave
as if there were an
alarm.
Red level
electrode LED 1 / 2 flashing
Alarm simulation in channel 1 or 2.
Off delay in progress,
signal outputs 1 / 2 close without a delay.
Red level
electrode LED 1 / 2 lit
Delay has elapsed,
output contacts open.
Signal outputs 1 / 2 closed.
Test is complete.
Operation, alarm and testing
Indicators and operation
Attention
Please check the following before fault diagnosis:
Supply voltage:
Is the level switch supplied with the voltage specified on the rating plate?
Wiring:
Does the wiring conform to the wiring diagram and your chosen switching
combination?
Configuration:
Are code switches
4
and
5
set correctly for the number of level electrodes?
Fault indications and troubleshooting
Indications, diagnosis and corrective action
Alarm 2 /
operating state LED
Level electrode 1
Test and diagnostic
button
Alarm 1 / operating
state LED
Level elec-
trode 2
Test
and diagnostic
button
Diagnostic LED
Fig. 12