25
System Malfunctions
– continued –
Systematic fault finding procedure for system malfunctions
– continued –
Assignment of signal LED / key / equipment:
LED 1 / Key 1: Limiter 1
LED 2 / Key 2: Limiter 2
LED 3 / Key 3: Limiter 3
LED 4 / Key 4: Limiter 4
Indication of system malfunctions in limiters 1 – 4
Limiters 1–4,
one or more limiters
have a malfunction
LED 1, 2, 3, 4,
one or more LEDs are flashing
slowly
Output contacts open instantaneously.
Signalling output is operating in the switching
mode.
Analysis of system malfunctions in limiters 1 – 4
Limiters 1–4,
one or more limiters
have a malfunction.
LED 1, 2, 3, 4,
one or more LEDs are
flashing slowly
Press and
hold down
corresponding
key
(key 1, 2, 3 or 4)
LED 1 is flashing slowly
Faulty communication between
limiter and controller,
HF interference
LED 2 and 3 are
flashing slowly
Excessively high temperature in the
terminal box of the electrode or the
temperature transmitter
LED 3 is flashing slowly
Sensor defective.
Analysis of system malfunctions in the controller
Malfunction
in control unit
LED bus status
is flashing slowly
Faulty communication within the CAN bus system.
HF interference
LED bus status
is illuminated
Control unit defective.
Output contacts open instantaneously.
Switched mode signalling output,
frequency 2.5 Hz.
LED Power is
flashing slowly
Bus supply voltage below 18 V.
Fig. 10
Malfunction alarm of control
unit and bus status LED
Mains supply LED
Control keys