6
NRG 26-21
Technical data
Level electrode
Service pressure
PN 40, 32 bar at 238 °C
Mechanical connection
Screwed G
¾
A, DIN ISO 228
Materials
Screw-in body: 1.4571, X6CrNiMoTi17-12-2
Electrode rod insulation: PTFE
Length of installation
at 238°C
373
477
583
688
794
899
1004
1110
Measuring range
300
400
500
600
700
800
900
1000
Length of installation
at 238°C
1214
1319
1423
1528
1636
2156
Measuring range
1100
1200
1300
1400
1500
2000
Weight
Approx. 1.8 kg (NRG 26-21 L=1000 mm)
Electronic module NRV 2-29
Supply voltage
12 V DC
Response sensitivity
Range 1:
Water
≥
0.5
µ
S/cm
Range 2:
Water
≥
20
µ
S/cm
Range 3:
Fuel oil EL
ε
r
2,3
Output
≥ 0 – ≤ 7 V DC, level proportional
Adjustors
1 Code switch with 6 poles for setting the measuring range
Housing
PPO (Noryl
®
)
Electrical connection
1 Screw-type terminal strip with 3 poles, cable gland with integrated cable clamp M 16
Protection
IP 65 to EN 60529
Admissible ambient temperature
Max. 70 °C