17
Examples of Installation
- continued -
NRG 111-50
Fig. 19
Protection tube (provided
on site) if electrode is used
as internal water-level
limiter
Fig. 21
Level pot ≥ DN 80 if
electrode is used as
external water level
limiter
Fig. 20
Inclined installation, e. g.
in steam boilers
g
Flange PN 40, PN 63, PN 160, DN 50, DIN EN 1092-01 (for one electrode)
Flange PN 40, PN 63, PN 160, DN 100, DIN EN 1092-01 (for two electrodes)
GESTRA hat flange PN 320, DN 50, DIN EN 1092-01 (NRG 111-50)
h
For the approval of the boiler standpipe with connecting flange the relevant regulations must
be considered.
l
Vent hole
Provide vent hole as close to the boiler wall as possible!
j
High water HW
k
Electrode tip d = 8 mm
l
Protection tube DN 80 (in France according to AFAQ ≥ DN 100)
m
Protection tube DN 100
n
Electrode distance ≥ 14 mm (air gap and creepage distance)
o
Low water LW
p
Reducer DIN 2616-2, K-88.9 x 3.2-42.4 x 2.6 W / DIN 2616-2, K-114.3 x 3.6-48.3 x 2.9 W
Key
g
h
i
k
j
∅
20
20
DN 50
G1
∅
20
≤ 90°
≥10
l
o
p
n
45°
max.
1000
20
≥14
≥14
≥14
g
g
j
p
o
≥ DN 20
G¾
≥ 20
≥ DN 20
≥ DN 20
≥ 10
190
Centre distance