End connections
The equipment is available with the following end
connections:
Flanges
Name plate
The following items are indicated on the name
plate:
Manufacturer
Type designation
Nominal size
Pressure rating
Design temperature
Design pressure
Max. service temperature
Max. admissible differential pressure
CE marking
Date of manufacturing
The following items are indicated on the equipment
body:
Material
Batch code
Direction of flow
Application of European Directives
Pressure Equipment Directive
The equipment conforms to this directive (see
"Manufacturer's Declaration" section) and can be
used for the following media:
Fluids of group 2
ATEX Directive
The equipment has classification: CE Ex II 2G/D c X.
For use in potentially explosive atmospheres in
zones (surrounding atmosphere to Directive
1999/92/EC) 1, 2, 21 and 22, please read and
observe the following information:
The sign "X" in the Ex label signifies that operation
at an excessive surface temperature caused by the
medium must be avoided. The equipment itself
does not generate additional surface temperatures.
Once installed, static electricity may arise between
the equipment and the connected system. During
use in potentially explosive atmospheres, the
discharge or prevention of possible electrostatic
charging is the responsibility of the manufacturer or
owner of the system. If there is a possibility that
medium might escape, e.g. via actuating devices
or leaks in screwed couplings, the manufacturer or
owner of the system must take this into
consideration when dividing the area into zones.
Task and function
The equipment is used for automatically draining off
large volumes of condensate where pressure and
the condensate flowrate fluctuate greatly.
The equipment vents automatically during start-up
and operation.
The equipment may also be used as a peak limiter.
You can infinitely adjust the aperture of the stage
nozzle using the handwheel.
The flow of medium is displayed in the integrated
VAPOSCOPE.