Attention!
Risk of equipment damage or malfunction
if incorrectly installed.
Make sure that connections on the
steam generating unit have been
correctly produced.
To prevent water hammer, route the
pipe downstream from the equipment
with a downhill gradient.
Always make sure the actuator has an
inclination of less than 90 ° when
installing the equipment.
Please note the following points to ensure correct
connection to the pressure vessel:
The equipment must be connected at about
100 mm below the low level line in the steam
generating unit.
Do not connect the equipment on the floor of
the steam generating unit.
Do not connect the equipment in the steam
zone of the tank.
Note the following instructions for different
installation positions:
We recommend installing the equipment
horizontally with the nozzle needle upright.
If the equipment is installed with the nozzle
needle inclined or horizontal, provide support for
the actuator.
Please contact the manufacturer if you wish to
install the equipment in a different position.
To allow easy access for routine servicing and
exchanging components observe the indicated
withdrawal distances and allow for clearances to
adjacent installation parts.
Make sure that the pipe system of the plant is
clean.
Make sure that the equipment is free from
foreign matter.
Install the equipment in the desired, permitted
installation position.
Make sure that the equipment is safely mounted
and that all connections are made correctly.
DANGER
Danger of death from electric shock!
Make sure the drive is disconnected
from the mains connection during all
work.
Have specialist personnel handle the
mains connection.
Specialist personnel must have knowledge and
experience of working on electrical systems with
the required operating voltage and current.
Have specialist electrical technicians connect
the actuator.
Make sure that specialist personnel follow all
instructions in the installation & operating
manuals for the actuator and control system.
Содержание BA 46
Страница 1: ...Continuous blowdown valve BA 46 BA 47 BAE 46 BAE 47 Original Installation Instructions 818609 04 ...
Страница 3: ...Dimensions and weights 39 Pressure temperature ratings 43 Manufacturer s Declaration 45 ...
Страница 19: ...19 Flow diagram for DN 15 to DN 32 capacity range up to 310 kg h ...
Страница 20: ...20 Flow diagram for DN 15 to DN 32 capacity range up to 1 020 kg h ...
Страница 21: ...21 Flow diagram for DN 15 to DN 32 capacity range up to 2 120 kg h ...
Страница 22: ...22 Flow diagram for DN 40 and DN 50 capacity range up to 1 340 kg h ...
Страница 23: ...23 Flow diagram for DN 40 and DN 50 capacity range up to 4 500 kg h ...
Страница 24: ...24 Flow diagram for DN 40 and DN 50 capacity range up to 6 300 kg h ...
Страница 39: ...39 Technical data Dimensions and weights BA BAE ...
Страница 46: ...46 ...
Страница 47: ...47 ...