          Meter Value 3 = 0x38(KWh)

 

          Meter Value 4 = 0xA3(KWh)

 

 
          Accumulated  power  consumption  (KW/h)  =  (Meter  Value  2*65536)  +  (Meter 

Value 3*256) + (Meter Value 4) = 800.35 (KW/h)

 

 
2-2-3 Clearing accumulated power consumption

 

     

 

Meter Reset Command: [Command Class Meter, Meter Reset]

 

 

2-2-4 AC load Voltage (V)

 

When receiving Meter Get Command, it will report Meter Report Command to the 
node.

 

 

Meter Get Command: [Command Class Meter, Meter Get, Scale =0x04(V)] 

 

 

 

Meter Report Command:

 

[Command Class Meter

Meter Report

Rate Type = 0x01

Meter Type = 0x01

Precision = 1

Scale = 4

Size = 2

Meter Value(V)]

 

 
Example:

 

Scale = 0x04 (V)

 

Precision = 1 

 

Size = 2 Bytes (V)

 

Meter Value 1 =    0x09(V)

 

Meter Value 2 =    0x01(V)

 

AC load Voltage =    (Meter Value 1*256) +(Meter Value 2)= 230.5 (V)

 

 
2-2-5 AC load current ( 

I

 )

 

        When receiving Meter Get Command, it will report Meter Report Command to the 
node.

 

Meter Get Command: [Command Class Meter, Meter Get, Scale =0x05(I)]

 

Meter Report Command:

 

[Command Class Meter

Meter Report

Rate Type  =  0x01

Meter Type  = 0x01

Precision = 2

Scale = 5

Size = 2

Meter Value(

I

)]

 

 
Example:

 

Scale = 0x05 (

I

)

 

Precision = 2 

 

Size = 2 Bytes (

I

)

 

Meter Value 1 = 0x01(

I

)

 

Meter Value 2 = 0x21(

I

)

 

AC load current = (Meter Value 1*256) +(Meter Value 2) = 2.89 (A)

 

 
2-2-6 load power factor (PF)

 

    When receiving Meter Get Command, it will report Meter Report Command to the 

node.

 

 

Meter Get Command: [Command Class Meter, Meter Get, Scale =0x06(PF)]

 

Meter Report Command:

 

[Command Class Meter

Meter Report

Rate Type  =  0x01

Meter Type  = 0x01

Precision = 2

Scale = 6

Size = 1

Meter Value(PF)

 

 
Example:

 

Scale = 0x06 (PF)

 

Precision = 2

 

Size = 1 (PF)

 

Meter Value 1 = 0x63(PF) (It means that the load power factor is 0.99)

 

 
3.    Z-Wave’s Configuration

 

 

Configuration

 

Parameter

 

Function

 

Size

 

(Byte)

 

Value

 

Unit

 

Default

 

Description

 

1

 

Manual Switch 

Report mode

 

1

 

0-1

 

 

1

 

0 : Disable

 

1 : Enable

 

2

 

switch Working 

Timer

 

1

 

1-11

 

10min

 

6

 

6*10min=1 hour

 

3

 

Watt Meter 

Report Period

 

2

 

0x01-

 

0x7FFF

 

5s

 

720

 

720*5s=3600s=1 hour

 

4

 

KWH Meter 

Report Period

 

2

 

0x01-

 

0x7FFF

 

10min

 

6

 

6*10min=1 hour

 

5

 

Threshold of

 

current for Load

 

caution

 

2

 

10-1500

 

0.01A

 

1500

 

1500*0.01A = 15A

 

6

 

Threshold of

 

KWh for Load

 

caution

 

2

 

1-10000

 

1KWh

 

10000

 

10000*1KWh= 

10000KWh

 

7

 

Watt differential 
report mode

 

1

 

0-1

 

 

 

1

 

0: Disable

 

1: Enable

 

Содержание GPB-7000

Страница 1: ...ather Be sure to isolate or switch off power source before installing or maintenance Do ensure that the power supply circuit protected by a 16A circuit breaker or suitable equivalent fuse IMPORTANT In...

Страница 2: ...again and hold for 5 seconds 3 IDs are excluded LED 2 second on 2 second off Adding a node ID allocated by Z Wave Controller means inclusion Removing a node ID allocated by Z Wave Controller means ex...

Страница 3: ...the switch will turn off Programming 1 Basic Command Class Binary Switch Command Class GPB 7000 will respond to BASIC and BINARY commands that are part of the Z Wave system 1 1 BASIC_GET BINARY_SWITCH...

Страница 4: ...0x08 Command_Class_Alarm Alarm_Report Alarm Type 0x08 Alarm Level 0xFF Alarm Level 0xFF Alarm Level 0xFF Alarm Level 0xFF 2 2 Response to Meter Get Command The switch will report its 1 instant Power...

Страница 5: ...sion 2 Scale 5 Size 2 Meter Value I Example Scale 0x05 I Precision 2 Size 2 Bytes I Meter Value 1 0x01 I Meter Value 2 0x21 I AC load current Meter Value 1 256 Meter Value 2 2 89 A 2 2 6 load power fa...

Страница 6: ...the Range of the setting value is from 10 to 1500 and the default value is 1500 3 6 Threshold of KWh for Load Caution This is a warning when the KWh of load over the preset threshold value If the set...

Страница 7: ...40M in door and 100M in outdoor line of sight Operating Temperature 0 C 40 C 85 humidity Storage Temperature 20 C 60 C Location Indoor use only Frequency Range 868 40MHz 869 85MHz EU 908 40MHz 916 00M...

Страница 8: ...ations However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be deter...

Отзывы: