4
2-1-1 On/Off Event Report
When “on” or “off ” state has been changed, it will send Binary Switch Report to the
node of Grouping 1.
Binary Switch Report
ON:[Command Class Switch Binary, Switch Binary Report, Value =255(0xFF)]
OFF:[Command Class Switch Binary, Switch Binary Report, Value =0(0x00)]
2-1-2 Instant Power Consumption vary over 5% report
When the power consumption of load vary over 5%, it will send Meter report to the
nodes of Grouping 1.
Meter Report Command: [Command Class Meter
,
Meter Report
,
Rate Type =
0x01
,
Meter Type = 0x01
,
Precision = 1
,
Scale = 0x02
,
Size = 4
,
Meter
Value(W)
2-1-3 Overload alarm report
When GPB-7000detects the current is more than 16A, it will send Alarm Report to
Group 1 node. After detecting overload state and sending this alarm report, GPB-
7000 will turn off the relay automatically and lockout the “
” button. The only thing to
do is disconnecting GPB-7000 and reduce the load. Then reconnect GPB-7000 and
it will work again.
The content of Alarm Report
Alarm report command:
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x08,
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x08,
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x08,
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x08,
Alarm Level = 0xFF]
Alarm Level = 0xFF]
Alarm Level = 0xFF]
Alarm Level = 0xFF]
2-2 Response to Meter Get Command
The switch will report its (1) instant Power Consumption (Watt) or (2) accumulated
power consumption(KWH) or (3)
AC load Voltage (V) or (4)
AC load current ( I ) (5)
load power factor (PF) to Z-Wave Controller after receive the Meter Get Command
from Z-Wave Controller.
2-2-1 Instant Power Consumption (Watt) of load
When receiving Meter Get Command, it will report Meter Report Command to the
node asked.
Meter Get Command: [Command Class Meter, Meter Get, Scale =0x02(W)]
Meter Report Command:
[Command Class Meter
,
Meter Report
,
Rate Type = 0x01
,
Meter Type =
0x01
,
Precision = 1
,
Scale = 2
,
Size = 4
,
Meter Value(W)]
Example:
Scale = 0x02 (W)
Precision = 1
Size = 4 Bytes (W)
Meter Value 1 = 0x00 (W)
Meter Value 2 = 0x00 (W)
Meter Value 3 = 0x03 (W)
Meter Value 4 = 0xEA (W)
Meter(W) = Meter Value 3 *256 + Meter Value 4 = 100.2W
2-2-2 Accumulated Power Consumption (KW/h)
When receiving Meter Get Command, it will report Meter Report Command to
the node.
Meter Get Command: [Command Class Meter, Meter Get, Scale = 0x00 KW/h)]
Meter Report Command: [Command Class Meter
,
Meter Report
,
Rate Type =
0x01
,
Meter Type = 0x01
,
Precision = 2
,
Scale = 0
,
Size = 4
,
Meter
Value(KWh)]
Example:
Scale = 0x00 (KWh)
Precision = 2
Size = 4 Bytes (KW/h)
Meter Value 1 = 0x00(KWh)
Meter Value 2 = 0x01(KWh)