ASTON CONSOLE SERIES INSTALLATION MANUAL
Auxiliary Heat Ratings
ECM Motors
Model
Rated
Voltage
Voltage
Min./Max.
Heater
Element
Watts
Fan
Motor
FLA
Heater
Element
FLA
Total
Unit
FLA
Min.
Circuit
Amp.
Max.
Fuse/
Brkr.
09-12
(1 kW)
208/60/1
197/254
818
2.45
3.93
6.4
8.0
10
230/60/1
197/254
1000
2.60
4.35
7.0
8.7
15
265/60/1
239/291
1000
2.50
3.77
6.3
7.8
10
09-12
(2 kW)
208/60/1
197/254
1636
2.45
7.86
10.3
12.9
20
230/60/1
197/254
2000
2.60
8.70
11.3
14.1
25
265/60/1
239/292
2000
2.50
7.55
10.1
12.6
20
15-18
(3 kW)
208/60/1
197/254
2454
2.45
11.80
14.3
17.8
30
230/60/1
197/254
3000
2.60
13.04
15.6
19.6
35
265/60/1
239/292
3000
2.50
11.32
13.8
17.3
30
Always refer to unit nameplate data prior to installation.
10/5/10
Blower Performance Data
For wet coil performance fi rst calculate the face velocity of the air coil (Face Velocity [fpm] = Airfl ow [cfm] / Face
Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400
fpm by 0.12in. wg. and 500 fpm by 0.16 in. wg.
ECM Motors
Model
CFM
Low Speed
Medium Speed
High Speed
09
300
325
400
12
300
325
400
15
350
450
600
18
350
450
600