800 523-9938
703 368-2101
Fax: 703 368-1078
E-Mail: [email protected]
GEORATOR Corporation
The Frequency Converter People Since 1950
9617 Center Street
Manassas, VA 20110
Interface
Model
Capacity
Input
Protection
Output
Environment
Dimensions
Weight *
Over/Under Voltage
Overload
Output Short Circuit
Over Temperature
Voltage Regulation
Frequency (select one)
Frequency (select one)
Phase
Crest Factor
Overload Capacity
Efficiency
Humidity
Operating Temperature
Audible Noise
W x H x D (mm)
Surge
Distortion (THD)
W x H x D (in)
Kilograms
Pounds
Triathlon III UPS Specifications - 1 Phase Input to 1 Phase Output Model, 20 KVA
1 Phase 100, 110, 115, 120, 200, 208, 220, 230, or 240V ± 20%
20 KVA
T3UPS-11-20K
50 or 60 Hz ± 5% (Optional 400Hz)
100, 110, 115, 120, 200, 208, 220, 230, or 240V ( ± 5% adjustable)
± 1% at Linear Load
50 or 60Hz ± 0.1Hz (Optional 400Hz)
1 Phase, 2W+G (Optional 3W)
< 2% @ 0-100% Non-linear Load
3:1
125% for 15 Minutes, 150% fro 10 Minutes, > 150% for 1 minute
>=91%
Power Walk In
0-100% < 20 seconds
Power Factor
0.8
Alarm
Rectifier, Reserve, Bypass NFB
Auto-shutdown 1 minute, Auto Restore when back to normal
Auto-shutdown
MOV / Input & Output (FCC CLASS A)
EN50091-2 Approved
0° – 40° C
0 - 90% Non-condensing
< 65 dB at 1 meter
550*1,600*800
21.7*63.0*31.5
380.0
837.8
Battery
Type - Quantity
Backup Time **
Minutes - Minimum
HR1234W - 58 ea.
10 min.
EMI/EMC
w/o batteries
Contact Closure, RS-232/485
Support MEGATEC RUPS, MEGATEC RUPSII / UPSilon 2000 UPS monitoring software
Indicators
LCD
LED
Real Time Status, Data or Historical Events, Parameters, Real Time Clock,
Inverter & Alarm
Up to date information (Status) to the User & Audible Alarm
Battery
Kilograms
Pounds
170.0
374.8
Weight
Voltage
(select one individual voltage)
Voltage
(select one individual voltage)
Galvanic Isolation
Input & Output True Galvanic Isolation
* Weights based on 220V IN and OUT. Weights may vary based on input/output frequency/voltage
** Longer backup times (to 8 hours) are available from standard models; custom specifications also available.
Содержание Triathlon III T3UPS-11-20K
Страница 18: ...1 7 Dimension Drawings 10KVA 60KVA OUTLINE DRAWING 1 13 ...
Страница 19: ...10KVA 60KVA INTERIOR DRAWING 1 14 ...
Страница 20: ...75KVA 160KVA OUTLINE DRAWING 1 15 ...
Страница 21: ...75KVA 160KVA INTERIOR DRAWING 1 16 ...
Страница 22: ...175KVA 320KVA OUTLINE DRAWING 1 17 ...
Страница 23: ...175KVA 320KVA INTERIOR DRAWING 1 18 ...
Страница 24: ...INTER PCB DIAGRAM 1 19 ...
Страница 31: ...1 ...
Страница 35: ...3 3 ...
Страница 70: ...ONE TO TWO SERIAL REDUNDANCY 8 3 ...
Страница 77: ...Appendices Additional Data on Options UPSCOMTM UPSCALLTM DCMANTM ...
Страница 80: ...3 ...