The UPM Controller 

The  Unit  Protection  Module  (UPM)  board, 
shown in 

Figure 1

, is used in all ‘configure-to-

order’ applications.  

The controller provides short cycling and 

refrigerant circuit protection. The controller is 
a  plug  and  play  device  which  also  has 
options  for  freeze  and  condensate  overflow 
protection if sensors are installed. 

The  controller  is  programmed  and  it  is 

backwards compatible for most functions of 
its  earlier  versions.  This  controller  can  be 

used  as  replacement  for  the  following  part 
numbers: 

1.

 

641-176 

2.

 

641-187 

3.

 

641-225 

4.

 

641-244 

 
User settings such as reset on power versus 
“Y  call”  and  the  number  of  faults  prior  to 
lockout among others can be adjusted by a 
qualified technician when replacing previous 
revisions.  

 

 

Figure 1 - UPM Controller 

 

Содержание 8733 800-259

Страница 1: ...1 8733 800 259 KIT Replacement Kit 641 176 641 187 641 225 641 244 IOM...

Страница 2: ...THE UPM CONTROLLER 3 SPECIFICATIONS 4 KIT INCLUDES 5 INSTALLATION PROCEDURE 5 Remove Old Board 5 Mounting holes 5 Wiring Installation 6 Sensor Installation 8 FINAL PROCEDURES 10 Table of Contents 2...

Страница 3: ...ensate overflow protection if sensors are installed The controller is programmed and it is backwards compatible for most functions of its earlier versions This controller can be used as replacement fo...

Страница 4: ...purposes dry contact Normally Open NO Inputs Four 4 inputs Dedicated inputs for High Pressure Switch HPC Low Pressure Switch LPC Freeze Sensor FREEZE 10 K 77F Thermistor Condensate Overflow Sensor CON...

Страница 5: ...Remove Old Board 1 Locate existing UPM in unit electrical box 2 Verify old part number on the old board as one of the four listed on page 3 3 Take a picture or LABEL all wires currently present and a...

Страница 6: ...circuit board as shown in Figure 2 2 Secure controller to unit by using four 1 long 6 screws along with the tubular sleeves Figure 2 Plastic Stand Off Wiring Installation Reconnect the wires using th...

Страница 7: ...an existing screw that secures an existing component IMPORTANT Ground Do not forget to ground the board If a connection is not available ground the terminal by Avoid sharp edges on unit cabinet durin...

Страница 8: ...5 Figure 5 Freeze Sensor s New Location Once the sensor has been relocated use wire ties and cork tape to secure and insulate sensor as shown below in Figure 6 Figure 7 and Figure 8 If this is a new...

Страница 9: ...Figure 6 Sensor with Wire Ties Figure 7 Wire Tied Sensor with Cork Tape Figure 8 Final Sensor Installation with Insulating Tape 9...

Страница 10: ...and their corresponding faults are shown 1 High Pressure Switch 2 Low Pressure Switch 3 Freeze Protection 4 Condensate Sensor 5 Brownout Protection A COND error will result in a hard lockout requiring...

Страница 11: ...11...

Страница 12: ...12 Figure 9 UPM Typical Wiring Components...

Страница 13: ...13 Figure 10 UPM Operation Flow Chart...

Страница 14: ...14 6720220404 REV 8 12...

Отзывы: