Measurement  error  due  to  the  resistance  of  the  connecting  cable  needs  to  be  compensated  in  the 
following way: 

Move  the  jumper  on  the  circuit  board  of  the  heat  sensor 
(RGT-ET) to the position shown in the picture. By doing 
that, you replace the heat sensor with a 10Kohm reference 
resistor.  Now  25°C  is  supposed  to  be  displayed  by  the 
control  unit.  If  you  read  any  other  value,  then  set  the 
difference  as  a  P1  Tcorr  value 

with  opposite 

sign.  (The 

procedure  is  detailed  under 

Initial  setup

.)  Return  the 

control  unit  to  normal  operation,  25°C  should  be 
displayed.  If  correct,  place  the  jumper  of  the  heat  sensor 
unit back to its original position to activate the real sensor 
instead of the reference resistor. 

 
 
Important: 

If an external heat sensor is connected, the jumper JP1 (next to the display) of the control 
unit must be placed in position 3 (closer to the display)! 

 

Valid: 

from

 

FRW Q2686 v1.3 

 

 

Manufacturer:

 

Geocoop 

 

 

 

Address: Szugló u. 54. 

    Budapest 

    Hungary 

    H-1145 

 

 

 

Telephone: +36 1 367 5961, +36 1 242 5161 

            Fax: +36 1 430 0914 

 

 

 

E-mail: 

[email protected]

 

 

                       Web: www.geocoop.hu 

Содержание RGT-03

Страница 1: ...C Programming 7 days 4 set point day Relay switch Single Pole Double Throw voltage 24V 230VAC load 6A ohmic 3A inductive Relay life 100 000 switches Power input 10 13VDC max 110 mA Operating temperat...

Страница 2: ...it can be exposed to direct sunlight Mounting The opening for the cables and the mounting holes are located on the bottom of RGT 03 It is advisable to mount the unit above a wall mount box by two scre...

Страница 3: ...o the actual application Jumper JP3 and button S1 S2 and S3 will be used 1 Turn power on and wait for displaying the time date 2 Make JP3 shorted by the supplied connector 3 Scroll the menu up or down...

Страница 4: ...switch to 21 C lower temp limit upper temp limit P62 Time Saturday 2 switch time 12 00 00 00 23 59 P62 Ref Saturday 2 temperature to switch to 21 C lower temp limit upper temp limit P63 Time Saturday...

Страница 5: ...on off by pressing the OK button Please note Do not leave the illumination turned on permanently because the produced heat can lead to false temperature measurement In operation two parameters can be...

Страница 6: ...a warning message to this number if the measured temperature is under the lower or above the upper temperature limit by 2 C In case a prepaid SIM card is used with the control unit you can check the b...

Страница 7: ...minute for the unit to restart before check The RGT 03 is able to function as a simple thermostat even with no SIM card installed If so the SIM ERROR message will be displayed for 10 seconds after th...

Страница 8: ...as a P1 Tcorr value with opposite sign The procedure is detailed under Initial setup Return the control unit to normal operation 25 C should be displayed If correct place the jumper of the heat sensor...

Отзывы: