RGT-03 GSM Thermostat 

 

 

 

3                                              ML_RGT03_V5_english.doc 

 

The wiring should be done in accordance with local regulations. The use of a maximum 10A fuse is 
highly recommended. 

Please note:  

The person who carries out the installation must have basic knowledge on electricity. 
Make sure the power is cut off before any operation! 

 

Initial setup 

First, prepare the SIM card by a GSM phone and insert into the SIM holder. (See previous picture!)  

SIM preparation: Insert the SIM card into a common GSM phone. In the menu, find and disable the 
security  function  that  makes  the  phone  asking  for  PIN  number  on  star  up.  Next,  type  the  phone 
number that belongs to the SIM card in the ’Own Number’ menu – or similar. (That is only to allow 
the  control  unit  to  acquire  the  time  from  the  GSM  network  during  turning  on.  However,  it  is  not 
essential to do, since it can be doing with SMS command later, when the control unit is turned on.) 
Now the card is ready to be inserted into the control  unit. 

 

Before  reinserting  the  cover,  the  initial  setup  is  to  be  done  to  adapt  the  RGT-03  to  the  actual 
application.  
Jumper JP3 and button S1, S2 and S3 will be used. 
 
1.

 

Turn power on and wait for displaying the 
time/date. 

2.

 

Make  JP3  shorted  by  the  supplied 
connector. 

3.

 

Scroll the menu up or down with button S1 
and S2 to check each parameter. Select the 
one you need to change by pressing button 
S3. A flashing value will then indicate that 
the value is ready to be changed. Now use 
button  S1  and  S2  to  alter  the  value.  Press 
S3 repeatedly to save the value and return 
to  the  menu.  The  chart  below  shows  the 
menu  points,  the  default  values,  and  the 
range of possible adjustment. 

 

Display 

Meaning 

Default 

Possible adjustment 

H/C Type 

type of heating/cooling system 

See separate table! 

P1  Tcorr 

temperature shift 

0°C 

-3 … + 3°C 

P2  Llim 

lower temperature limit 

5°C 

5 … 15°C 

P3  Ulim 

upper temperature limit 

40°C 

21 … 40°C 

P4  Pprot 

pump protection 

OFF 

OFF/ON 

P01 Time 

Sunday 1. switch time 

08:00 

00:00 – 23:59 

P01 Ref 

Sunday 1. temperature to switch to 

21°C 

lower temp. limit – 
upper temp. limit 

P02 Time 

Sunday 2. switch time 

12:00 

00:00 – 23:59 

P02 Ref 

Sunday 2. temperature to switch to 

21°C 

lower temp. limit – 
upper temp. limit 

P03 Time 

Sunday 3. switch time 

17:00 

00:00 – 23:59 

P03 Ref 

Sunday 3. temperature to switch to 

21°C 

lower temp. limit – 
upper temp. limit 

Содержание RGT-03

Страница 1: ...C Programming 7 days 4 set point day Relay switch Single Pole Double Throw voltage 24V 230VAC load 6A ohmic 3A inductive Relay life 100 000 switches Power input 10 13VDC max 110 mA Operating temperat...

Страница 2: ...it can be exposed to direct sunlight Mounting The opening for the cables and the mounting holes are located on the bottom of RGT 03 It is advisable to mount the unit above a wall mount box by two scre...

Страница 3: ...o the actual application Jumper JP3 and button S1 S2 and S3 will be used 1 Turn power on and wait for displaying the time date 2 Make JP3 shorted by the supplied connector 3 Scroll the menu up or down...

Страница 4: ...switch to 21 C lower temp limit upper temp limit P62 Time Saturday 2 switch time 12 00 00 00 23 59 P62 Ref Saturday 2 temperature to switch to 21 C lower temp limit upper temp limit P63 Time Saturday...

Страница 5: ...on off by pressing the OK button Please note Do not leave the illumination turned on permanently because the produced heat can lead to false temperature measurement In operation two parameters can be...

Страница 6: ...a warning message to this number if the measured temperature is under the lower or above the upper temperature limit by 2 C In case a prepaid SIM card is used with the control unit you can check the b...

Страница 7: ...minute for the unit to restart before check The RGT 03 is able to function as a simple thermostat even with no SIM card installed If so the SIM ERROR message will be displayed for 10 seconds after th...

Страница 8: ...as a P1 Tcorr value with opposite sign The procedure is detailed under Initial setup Return the control unit to normal operation 25 C should be displayed If correct place the jumper of the heat sensor...

Отзывы: