background image

Electrical installation

The ECO 375 comes prepared for external connection of 

internet and display, BMS connection and Genvex 

 accessories.

As standard, the system is supplied with a 2.5 metre 230V 

power supply cable with schuko connector.

See wiring diagrams and operating instructions for the 

Optima 270 for more information.

In general, all electrical connections to the ECO 375 must 

be executed by an authorised electrician.

Important!

For functional and safety reasons, the unit must be con-

nected to a socket with grounding matched to the plug 

connection.

Control and calibration of the system

To achieve optimal operation of the system, it must be  

commisioned using specialist ventilation measuring 

equipment. If it is desired to put the system into operation 

before calibration, the following approach can be taken:

Before putting the system into operation

1. Check that the Genvex unit is correctly mounted and that 

all the ducts are properly insulated.

2. Check that the door can be opened so that it is possible 

to service and maintain the unit.

3. Check that the filters are clean (they may be dirty after 

installation).

4. Set all supply air valves so that the valve closest to the 

unit is opened 3 turns from the closed position and the 

outer one is opened 8 turns from the closed position. The 

intermediate valves are opened between 4 and 7 turns, 

depending on how close they are to the unit.

The system can now be put into operation and run until   

the system is commisioned using specialist ventilation 

 measuring  equipment.

Optimal initial calibration of the system

Genvex recommends that the ventilation unit should be 

commisioned by an authorised Genvex dealer before it is 

put into operation.

Before starting the initial calibration, check that the 4 

points in the section on control and calibration of the 

system have been performed. Then start the unit:

Set the initial basic ventilation value, which is speed 2. To 

reduce energy consumption as much as possible, first 

adjust the main air flows to the desired air flow by adjusting 

the speed of the fans via the control panel.

Then adjust the supply air and exhaust air valves with air 

measuring equipment (during the initial calibration of the 

valves, remember to lock them and to turn the baffle plate 

in the supply air valves so that the air blows in the right 

direction).

Then check the main air flows again and fine-tune them 

using the outdoor air and exhaust air valves (remember to 

lock the position of the valves after initial calibration).

10   

Содержание ECO 375

Страница 1: ...INSTALLATION MANUAL ECO 375 Mechanical ventilation with passive heat recovery A...

Страница 2: ...s in warm rooms 9 Post heating of supply air 9 Electrical installation 10 Control and calibration of the system 10 Optimal initial calibration of the system 11 System maintenance 11 Recommended mainte...

Страница 3: ...guidance on using the appliance in a safe way and under stand the dangers involved Children must not play with the appliance Cleaning and user maintenance must not be performed by children without su...

Страница 4: ...n integrated water level switch can also be purchased as an accessory which ensures that the system is stopped and an alarm is shown in the display in the event of problems with the condensate drain e...

Страница 5: ...re cases and in combination with inappropriate installation conditions it may cause unsatisfactory noise or vibration nuisances As a general rule it is always recommended installing the technical syst...

Страница 6: ...vailable in a vertical version as shown below Weight 40 kg 1 Outdoor air 2 Exhaust 3 Extract air 4 Supply air 5 Supply air fan 6 Exhaust fan 7 Outdoor air filter 8 Extract filter 9 Bypass duct 10 IO c...

Страница 7: ...e important that the condensate drain is executed correctly and that the drain pipe slopes slightly towards the sewer connection An ordinary 32 mm water trap can be connected directly to the ventilati...

Страница 8: ...fort and minimal impact from the sun s heat Recommended minimum horizontal distance between air intake and exhaust 3 metres Recommended minimum vertical distance between air intake and exhaust 1 metre...

Страница 9: ...ic from heating the fresh air in the summer Be sure to seal the termination where the outgoing duct passes through the roof or gable to prevent condensation damage Insulation of ducts in heated rooms...

Страница 10: ...o that the valve closest to the unit is opened 3 turns from the closed position and the outer one is opened 8 turns from the closed position The intermediate valves are opened between 4 and 7 turns de...

Страница 11: ...m using the fresh air and exhaust air valves remember to lock the position of the valves after initial calibration G4 Coarse Standard filter coarse filter class G4 F7 ePM1 Pollen filter fine filter cl...

Страница 12: ...problems If the conden sate drain does not work this may result in water damage in the home Removing the front plate When removing the EPS front plate start by removing the filter drawer and filters...

Страница 13: ...es to the right NOTE Please note that the temperature sensor on the exhaust side of the exchanger must be pulled out of the exchanger before the exchanger can be removed Remem ber to refit the sensor...

Страница 14: ...xchanger Clean with water 12 months Gaskets in general Check gaskets on the unit and make sure they are intact 12 months Supply air and exhaust air valves Check for dirt in supply air and exhaust air...

Страница 15: ...210 Exchanger aluminium 069211 Exchanger PET 069222 G4 filter Item no Description 069223 M5 filter 069224 F7 filter 060537 Bypass motor 069911 Built in electric preheating surface 1500 Watt optional 0...

Страница 16: ...the winter Fuse on control board has blown Unit is defrosting supply air fan runs at reduced speed Incorrect setting of Optima controls No exhaust air Defective exhaust fan Clogged exhaust filter Fus...

Страница 17: ...nsor T7 Extract air Sensor T4 Exhaust air Sensor T3 Outdoor air Sensor T1 Supply air Sensor T9 Option External stop EC fan Extract air Blue Yellow EC fan Supply air Blue Yellow EC fan Extract air 1x23...

Страница 18: ...18 DECLARATION OF CONFORMITY The declaration of conformity can be downloaded from www genvex com...

Страница 19: ...19 DE COMMISIONING INSTRUCTIONS Remove filters Remove countercurrent heat exchanger 1 and fans 2 Remove control board Remove built in electric preheating surface optional Remove bypass actuator 1 2 2...

Страница 20: ...ilies At the same time our system is an important element when it comes to saving energy in homes and in society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All...

Отзывы: