GenTran Silent Generator Скачать руководство пользователя страница 9

3.

 

Check that the DC BATTERY circuit breaker and the DC SOLAR INPUT circuit breaker (if a DC input power source is attached) 
are ON. 

4.

 

Turn OFF the DC BATTERY circuit breaker for 30 seconds, then turn ON.  If the Power System still does not function, please 
continue with Troubleshooting Guide, if problems persists, call Gen/Tran for technical support 

 
6.2 TROUBLESHOOTING GUIDE 

PROBLEM POSSIBLE 

CAUSE(S) 

SOLUTION 

SECTION 

 

A. Dedicated 20A 
circuit breaker in 
load center is 
tripping* 

 
 
 
 

1. Circuit breaker is smaller than 20A/2P 
2. Circuit breaker is not dedicated to unit 
3. Circuit breaker is defective  
 
* Some installation may require a 

dedicate 30A/2P circuit breaker, call 
Gen/Tran for additional information. 

1. Change to 20A/2P circuit breaker 
2. Remove all other loads on circuit breaker 
3. Replace circuit breaker 
 

2.1 

B. Power System 
shuts off during use 
in utility and/or 
backup mode. 

1. Connected loads exceed 4000W  
 
2. Batteries are over 80% discharged 
3. Inverter is defective 
 

1. Reduce connect loads to 4000W or less, system will 

restart in 6 seconds after loads are reduced 

2. Recharge batteries with AC and/or DC power 
3. Refer to Apollo User’s Manual  


 
 
 
 

C. Power system 
runs shorter than 
expected in backup 
mode 

1. Batteries are not fully charged 
 
2. Batteries have been damaged due to 

overuse or deep discharging 

3. Loads are larger than planned 

1. Ensure AC and/or DC power is connect to system 

and charge for 24 hours 

2. Test batteries and replace if damaged 
 
3. Turn off some loads 

 
SECTION 7 – FILING for TAX CREDITS 

When properly installed and used in conjunction with certain “qualified” properties, such as solar electric PV panels and 
windmills, the Silent Generator™ Power System may qualify for Federal, State and/or local tax credits and/or incentive grants, 
significantly reducing the initial investment required.  
 
Included in this Installation Manual is a Manufacturer’s Certification Statement, certifying that The Silent Generator™ Power 
System qualifies for  the Federal Tax Credit allowed under S1122 of the American Recovery and Reinvestment Act of 2009. 
Since Gen/Tran is not a tax or legal advisor, please consult with your tax and legal professional for more complete information.

 

 
SECTION 7 - AVAILABLE ACCESSORIES 

 

Model 14212 Power Outlet Box  

 

RJB12425 Cordset  

 
 
 

Содержание Silent Generator

Страница 1: ...es the right to change and update the manual and product at any time without prior notice No warranties expressed or implied including warranties of fitness for a particular purpose or merchantability or warranties arising from course of dealing or usage of trade are made regarding the information recommendations and descriptions contained herein In no event will Gen Tran Corporation be responsibl...

Страница 2: ...ill not eliminate this risk Do not operate the Silent Generator Power System with damaged or substandard wiring if it has received a sharp blow been dropped or otherwise damaged in any way Do not disassemble the Silent Generator Power System there are no user serviceable parts inside Contact Gen Tran to obtain service Attempting to service the unit yourself may result in a risk of electrical shock...

Страница 3: ...25 C Nominal Battery Voltage 48 Volts DC DC Input Operating Range 42 64 VDC Nominal AC Output 120 240 VAC 5 at 50Hz or 60 Hz Max Output Current 17 Amps 240 VAC 33 Amps 120 VAC Max Output Surge 25 C 200 7 Sec 150 30 Sec 115 30 Min Internal Battery Type Sealed Lead Acid AGM 2 types Deep Cycle repetitive discharge charge apps Float used occasionally for backup power Available Battery Capacity 800 Amp...

Страница 4: ... all times Temperature Ambient temperature not to exceed 104 F 40 C Ventilation Minimum room size of 6 x 6 x 8 Power 20A 2 Pole 125 250VAC dedicated power circuit Cabinet physical specifications Height 48 31 122 7 cm Width 19 16 48 7 cm Depth 28 3 71 9 cm Weight Model SG 4000 X 1 X 800AH storage approximately 930 lbs 422 kg Model SG 4000 X 2 X 1000AH storage approximately 1010 lbs 458 kg 1 5 UNLOA...

Страница 5: ...Power System down the ramp until the unit is on level ground Remove shipping brackets from pallet If the Silent Generator Power System is to be permanently mounted re attach the shipping brackets in reverse order mentioned above and anchor to floor 8 In case the cabinet will need to be moved to another location retain the shipping brackets ramps to move the Silent Generator Power System again They...

Страница 6: ...let Box and power inlet on the Silent Generator Power System 2 1 2 HARDWIRING CONNECTING A more permanent installation solution is to hardwire the Silent Generator Power System directly to a dedicated 20A 125 250VAC 2 Pole circuit breaker in your load center Cut the male plug off of the RJB12410 cordset and connect to the 20A 125 250VAC 2 pole circuit breaker in your load center following all loca...

Страница 7: ...7 2 3 THE USER INTERFACE LCD SCREEN OVER LOAD Systemoverload systemshutsoff loadswillnotbepowered disconnect loads will AUTO STARTafter6seconddelay SYSTEM OVERLOAD ...

Страница 8: ...ed SECTION 5 BATTERY MAINTENANCE and REPLACEMENT The Silent Generator Power System uses VRLA AGM sealed batteries full charged and ready to use from the factory The Silent Generator Power System should be installed and connected to an AC or DC power source within 90 days of purchase While the batteries have a design life of 10 years long periods between charging self discharging more frequent char...

Страница 9: ... in 6 seconds after loads are reduced 2 Recharge batteries with AC and or DC power 3 Refer to Apollo User s Manual 4 C Power system runs shorter than expected in backup mode 1 Batteries are not fully charged 2 Batteries have been damaged due to overuse or deep discharging 3 Loads are larger than planned 1 Ensure AC and or DC power is connect to system and charge for 24 hours 2 Test batteries and r...

Страница 10: ...la President Gen Tran Corporation August 16 2011 Disclaimer This certification statement is made as of August 16 2011 and Gen Tran Corporation makes no warranty as to the qualification of the products for federal tax credits if there are changes in requirements or applicable law after such date Gen Tran Corporation is not a tax advisor Taxpayers claiming a tax credit should consult a tax professio...

Страница 11: ... application use with any fuels ultra hazardous substances or other materials not pre approved by us b use as a component part of a product expressly warranted by another manufacturer c repair alteration or modifications by other than our approved service technicians d your failure to follow routine specified or suggested maintenance e removal of any tamper proof seals on the Product or f use of b...

Страница 12: ... 30009 Toll Free 1 888 GEN TRAN www gen tran com PN 50772 Rev A Gen Tran and PowerStay are registered trademarks of Gen Tran Corporation Silent Generator is a trademark of Gen Tran Corporation 2011 All rights reserved ...

Отзывы: