SECTION 3 - START-UP PROCEDURE 

1.

 

Confirm all wiring is correct and connections are tight. 

2.

 

Check that all input/output voltages and polarities are correct. 

3.

 

Turn ON the DC BATTERY circuit breaker. 

4.

 

Turn ON the DC SOLAR INPUT circuit breaker (if a DC input power source is attached). 

5.

 

The Silent Generator™ Power System will start in the inverter mode within 6 seconds. 

6.

 

Turn ON the 20A 125/250VAC circuit breaker providing AC power to the Silent Generator™ Power System. The system 
should switch to charge mode.  Please refer to the Apollo Inverter/Charger User’s Manual Section 5.2 for LCD screen 
descriptions. 

7.

 

Connect and turn on an appliance, such as a hair dryer or toaster, to the Silent Generator™ Power System, verify load 
wattage on LCD screen.  

8.

 

Disconnect the AC and DC power inputs to the Silent Generator™ Power System. The System will switch to back-up 
mode and continue to provide power to your appliance. Disconnect appliances from Silent Generator™ Power System 
and reconnect the AC and DC power inputs. 

 

SECTION 4 - CONNECTING LOADS 

Loads may be connected to the Silent Generator™ Power System thru the 2-15A VAC GFCI receptacles and/or thru the 20Amp 
125/250 VAC L14-20 receptacle.  Gradually add load, monitoring the Silent Generator™ Power System LCD to ensure the total 
loads do not exceed 4000w in total.  If the Silent Generator™ Power System is overloaded, it will shut off and not restart until 
loads are removed and then restart after 6 second delay.  All loads connected to the Silent Generator™ Power System will be 
provided power without interruption as along as the batteries are properly charged. 
 

SECTION 5 - BATTERY MAINTENANCE and REPLACEMENT 

The Silent Generator™ Power System uses VRLA AGM sealed batteries, full charged and ready to use from the factory.  The 
Silent Generator™ Power System should be installed and connected to an AC or DC power source within 90 days of purchase. 
While the batteries have a design life of 10 years, long periods between charging (self-discharging), more frequent 
charge/discharge cycles and extreme ambient temperatures can reduce actual battery life to 5 years or less.  While the batteries 
are maintenance-free, avoid frequent (daily) discharging of batteries to more than 50% of their capacity. Under extreme 
conditions, occasionally discharging to an 80% level is acceptable.  Total discharging will reduce battery life and permanently 
damage the batteries.  Gen/Tran recommends setting up a bi-annual maintenance schedule to check the condition of the 
batteries.  If batteries need to be replaced, ONLY use a Gen/Tran approved battery, call Gen/Tran for pricing and availability. Use 
of unauthorized batteries will void the warranty and could potentially damage the system. 
 

SECTION 6 – TROUBLESHOOTING 

Use the following troubleshooting guide to help diagnose problems. Thoroughly inspect the Silent Generator™ Power System  
wiring and cable connections.  Correct any wiring problems before performing any tests or replacing any components. 
 

6.1 BASIC TROUBLESHOOTING 

In case of a Silent Generator™ Power System failure, check the following BEFORE calling your installer: 
1.

 

Check that all power cord and cable connections are tight. 

2.

 

Check that the dedicated 20A 125/250VAC 2-Pole circuit breaker in your load center is ON. 

STANDBY 

                     

BAT    48.4V                     0.0 A

 

System is in STAND-BY, no loads 
will be powered

 

 

SYSTEM STANDBY

 

To enter STAND-BY mode,

 

press STANDBY button once

 

To exit  STAND-BY mode,

 

press STANDBY button once

 

Содержание Silent Generator

Страница 1: ...es the right to change and update the manual and product at any time without prior notice No warranties expressed or implied including warranties of fitness for a particular purpose or merchantability or warranties arising from course of dealing or usage of trade are made regarding the information recommendations and descriptions contained herein In no event will Gen Tran Corporation be responsibl...

Страница 2: ...ill not eliminate this risk Do not operate the Silent Generator Power System with damaged or substandard wiring if it has received a sharp blow been dropped or otherwise damaged in any way Do not disassemble the Silent Generator Power System there are no user serviceable parts inside Contact Gen Tran to obtain service Attempting to service the unit yourself may result in a risk of electrical shock...

Страница 3: ...25 C Nominal Battery Voltage 48 Volts DC DC Input Operating Range 42 64 VDC Nominal AC Output 120 240 VAC 5 at 50Hz or 60 Hz Max Output Current 17 Amps 240 VAC 33 Amps 120 VAC Max Output Surge 25 C 200 7 Sec 150 30 Sec 115 30 Min Internal Battery Type Sealed Lead Acid AGM 2 types Deep Cycle repetitive discharge charge apps Float used occasionally for backup power Available Battery Capacity 800 Amp...

Страница 4: ... all times Temperature Ambient temperature not to exceed 104 F 40 C Ventilation Minimum room size of 6 x 6 x 8 Power 20A 2 Pole 125 250VAC dedicated power circuit Cabinet physical specifications Height 48 31 122 7 cm Width 19 16 48 7 cm Depth 28 3 71 9 cm Weight Model SG 4000 X 1 X 800AH storage approximately 930 lbs 422 kg Model SG 4000 X 2 X 1000AH storage approximately 1010 lbs 458 kg 1 5 UNLOA...

Страница 5: ...Power System down the ramp until the unit is on level ground Remove shipping brackets from pallet If the Silent Generator Power System is to be permanently mounted re attach the shipping brackets in reverse order mentioned above and anchor to floor 8 In case the cabinet will need to be moved to another location retain the shipping brackets ramps to move the Silent Generator Power System again They...

Страница 6: ...let Box and power inlet on the Silent Generator Power System 2 1 2 HARDWIRING CONNECTING A more permanent installation solution is to hardwire the Silent Generator Power System directly to a dedicated 20A 125 250VAC 2 Pole circuit breaker in your load center Cut the male plug off of the RJB12410 cordset and connect to the 20A 125 250VAC 2 pole circuit breaker in your load center following all loca...

Страница 7: ...7 2 3 THE USER INTERFACE LCD SCREEN OVER LOAD Systemoverload systemshutsoff loadswillnotbepowered disconnect loads will AUTO STARTafter6seconddelay SYSTEM OVERLOAD ...

Страница 8: ...ed SECTION 5 BATTERY MAINTENANCE and REPLACEMENT The Silent Generator Power System uses VRLA AGM sealed batteries full charged and ready to use from the factory The Silent Generator Power System should be installed and connected to an AC or DC power source within 90 days of purchase While the batteries have a design life of 10 years long periods between charging self discharging more frequent char...

Страница 9: ... in 6 seconds after loads are reduced 2 Recharge batteries with AC and or DC power 3 Refer to Apollo User s Manual 4 C Power system runs shorter than expected in backup mode 1 Batteries are not fully charged 2 Batteries have been damaged due to overuse or deep discharging 3 Loads are larger than planned 1 Ensure AC and or DC power is connect to system and charge for 24 hours 2 Test batteries and r...

Страница 10: ...la President Gen Tran Corporation August 16 2011 Disclaimer This certification statement is made as of August 16 2011 and Gen Tran Corporation makes no warranty as to the qualification of the products for federal tax credits if there are changes in requirements or applicable law after such date Gen Tran Corporation is not a tax advisor Taxpayers claiming a tax credit should consult a tax professio...

Страница 11: ... application use with any fuels ultra hazardous substances or other materials not pre approved by us b use as a component part of a product expressly warranted by another manufacturer c repair alteration or modifications by other than our approved service technicians d your failure to follow routine specified or suggested maintenance e removal of any tamper proof seals on the Product or f use of b...

Страница 12: ... 30009 Toll Free 1 888 GEN TRAN www gen tran com PN 50772 Rev A Gen Tran and PowerStay are registered trademarks of Gen Tran Corporation Silent Generator is a trademark of Gen Tran Corporation 2011 All rights reserved ...

Отзывы: