Gentherm Global Power Technologies 8-7
P-5050
62553 Rev.8
f)
Using the output voltage adjustment, raise output voltage to a value where the VSR
will reset.
g)
To re-check the trip-point, lower output voltage and monitor opening of the VSR con-
tacts. Fine tune as required to achieve desire trip value.
h)
Reset output voltage to the desired normal operating value. Factory setting is either
14.1 or 28.0 V.
8.3 Enabling Temperature Compensation
Enabled temperature compensation will vary the output voltage by approximately 33mV/
ºC for 12V and 66mv/ºC for 24V. To Enable Temperature compensation use the following
procedure:
a)
Remove the customer load
b)
Set/verify SW1 on the Limiter board to the following (default) configuration, to disable
temperature compensation for adjustment of the output voltage:
a.
Switch 1- ON
b. Switch 2-OFF
c)
Connect a DC Voltmeter to the customer Load Terminals
d)
Turn the output voltage adjustment pot until the desired voltage is reached, per bat-
tery manufacturer’s recommended charging voltage for 25ºC, with no temperature
compensation.
e)
Set SW1 on the Limiter board to the following configuration, to enable temperature
compensation:
a.
Switch 1- OFF
b.
Switch 2- ON
8.4 Adjustment of Optional CP Interface System
An optional CP interface system is available for use with the model P-5050 TEG. This text
describes how to adjust the CP interface system, if applicable.
8.4.1 CP Power Output Adjustment
The 0-1Ω 300 W variable resistor, located inside the CP cabinet, may be used to adjust the
output power from the CP interface. This resistor may be connected in series or parallel with
the customer load. See Figure 24 for series connection and Figure 25 for parallel connec-
tion.
Содержание P-5050
Страница 4: ......
Страница 8: ......
Страница 39: ...Gentherm Global Power Technologies 5 7 P 5050 62553 Rev 8 Figure 14 Wiring Diagram P 5050 TEG for 12 or 24 V ...
Страница 41: ...Gentherm Global Power Technologies 5 9 P 5050 62553 Rev 8 Figure 16 Wiring Diagram P 5050 TEG for 6 7V ...
Страница 44: ...Gentherm Global Power Technologies 5 12 P 5050 62553 rev 8 ...
Страница 46: ...Gentherm Global Power Technologies 6 2 P 5050 62553 rev 8 ...
Страница 60: ...Gentherm Global Power Technologies 8 10 P 5050 62553 rev 8 ...