NOTE

:

The wiring to be used shall be in accordance with the

provisions of Article 210 of the National Electrical Code, ANSI/NFPA

70. Wire installation should be performed only by a licensed

electrician.

MOUNTING OUTLET BOX

Use a 2" x 3" switch box or a 4" square or octagon junction box.

Mount a box for each CO alarm. If wall mounting is desired, be sure

the box screws are oriented to upper right and lower left corners. Be

sure to use supplied Mounting Plate.

WIRING ONE ALARM

1. Run a minimum of 16 gauge, 2-conductor cable, plus ground (3

wires) to the junction box from a power supply. CO alarms shall

be connected to their own dedicated circuit. Use UL Listed Class

1 wire.

NOTE: The wiring to be used shall be in accordance with the

provisions of Article 300.3(b) 210 of the National

Electrical Code, ANSI/NFPA 70 as well as Article 210.

2. Make wire connections to the supplied plug-in connector as

follows: black to black, white to white, and connect the ground

wire to the metal outlet box.

NOTE:

RED-YELLOW WIRE AND BROWN-YELLOW WIRE: The

red-yellow wire and brown-yellow wire from the CO alarm is for

tandem connection only. DO NOT USE, AND DO NOT REMOVE

INSULATION CAP UNLESS CONNECTING ANOTHER CO ALARM,

SMOKE/CO ALARM OR SMOKE ALARM.

Figure 9

WIRING TWO OR MORE ALARMS

Tandem Installation

NOTE

:

All CO alarms in a tandem installation must be

controlled by the same fuse or circuit breaker. Otherwise tandem

units will not operate. Tandem will operate in the event of AC power

failure if battery is connected to the CO alarm.

LIMITATIONS:

A maximum of 12 CO alarms (CO1209) may be

connected together. Do not exceed 125 feet between each device.

Do not exceed 1125 feet between first and last CO alarm.

Wire used for interconnection shall be in accordance with article

760 of the latest edition of National Electrical Code (NFPA 70) and

must not exceed a resistance of 10 ohms.

Figure 10

LIMITATIONS:

Maximum of 12

CO alarms may be

connected

together. Do not

exceed 125 feet

between each CO

alarm. Do not

exceed 1125 feet

between the first

and last CO alarm.

NOTES ON TANDEM INTERCONNECTING MODELS

DO NOT

connect Gentex CO alarms to other manufacturers'

CO alarms.

No more than 12 Gentex models CO1209 may be tandem

interconnected.

All units connected in tandem

MUST

get their power from the

same circuit, that is, all CO alarms in tandem must be controlled

by the same fuse or circuit breaker.

After installation, to verify proper working conditions, all horns must

sound in this system.

When tandem interconnecting CO1209 Series to additional

CO1209 Series, GN-503 Series or GN-403 Series and the smoke

alarm horn sounds but are not synchronized and the CO horn

does not sound the red/yellow wire has been used. Use brown/

yellow wire.

Use red/yellow wire to tandem interconnect CO1209 alarms to

Gentex legacy products. Legacy products include 9120/9123

Series, 7100/7103 Series, 710CS/713CS Series, 7109CS/7139CS

Series, GN-200/GN-203 Series and GN-300/GN-303 Series.

Use brown/yellow wire to tandem interconnect CO1209 Series

alarms to additional CO1209 Series alarms, GN-403 Series and

GN-503 Series.

If the red/yellow wire is used to interconnect the GN-503 Series to

additional GN-503 Series, GN-400/GN-403 Series and CO1209

Series, the units will not be tandem inteconnected. The brown/

yellow wire

MUST

be used.

1. Run a minimum of 16 gauge, 3-conductor cable, plus ground (4

wires) to the first junction box from a power supply and between

all CO alarms that are to be connected together. Use UL Listed

Class 1 wire.

NOTE: When using both tandem connections, 4-conductor

cable, plus ground (5 wires) will be used.

2. Make wire connections to the supplied plug-in connector as

follows: black to black, white to white, 3rd conductor to the

red/yellow wire for legacy Gentex products or the brown/yellow

wire for new. The red/yellow wire or brown/yellow wire should be

stripped to make the connection. Connect ground wire between

metal outlet boxes.

Figure 11

RED-YELLOW OR

BROWN-YELLOW WIRE

UNINSULATED WIRE

EARTH GROUND -

FOR METAL BOXES

ONLY

3-WIRE CABLE

AND GROUND

120VAC

BLACK

WHITE

RED-YELLOW

BROWN-YELLOW WIRE

UNINSULATED WIRE

EARTH GROUND -

FOR METAL BOXES

ONLY

4-WIRE CABLE

AND GROUND

120VAC

BLACK

WHITE

550-0498

Pg. C-5

Содержание Smarter Vision CO1209 Series

Страница 1: ...exposed to a critical level of CO measured in parts per million or ppm within a specified time measured in minutes This CO alarm features a permanently installed sensor an indicator light and an 85dBA...

Страница 2: ...other appliances may also prevent alert persons from hearing the alarm horn This device is not intended for people who are hearing impaired CO alarms are not a substitute for life insurance Though th...

Страница 3: ...cupiable level of a dwelling unit including basements excluding attics and crawl spaces 3 Other locations where required by applicable laws codes or standards The installation of additional CO alarms...

Страница 4: ...DO NOT INSTALL THIS CO ALARM In garages kitchens furnace rooms or in any extremely dusty dirty or greasy areas Closer than 15 feet 4 6 meters from a furnace or other fuel burning heat source or fuel b...

Страница 5: ...1125 feet between the first and last CO alarm NOTES ON TANDEM INTERCONNECTING MODELS DO NOT connect Gentex CO alarms to other manufacturers CO alarms No more than 12 Gentex models CO1209 may be tande...

Страница 6: ...to add the telephone numbers of the emergency service provider and a qualified technician Once CO alarm is installed place one 1 label next to the CO alarm and place the other label near the fresh ai...

Страница 7: ...en using any of these materials near the alarm make sure the room is well ventilated The CO alarm is not washable DO NOT submerge the alarm in water Water can affect the sensor causing permanent damge...

Страница 8: ...entex postage prepaid You must also pack the CO Alarm to minimize the risk of it being damaged in transit You must also enclose a return address CO Alarms returned for warranty service should be sent...

Отзывы: