550-0636
Page 3
Gentex Super-Slide
®
Mounting Bracket:
Allows the installer to pre-wire the system, test for
system supervision, remove the signal head until
occupancy, switch out Gentex signals without
changing mounting brackets and has locking edge
connector for snap-in-place installation.
Gentex Checkmate
®
Instant Voltage Verification:
It is often necessary to confirm the voltage drop
along a line of devices. The access holes are
provided in the back of the terminal block to
allow the voltage to be measured directly without
removing the device. Typically this would be done
at the end of the line to confirm design criteria.
Most measurements will be taken using the S+ and
S- locations although access is provided to other
locations.
NOTICE
: CARE SHOULD BE TAKEN TO NOT SHORT
THE TEST PROBES.
FOR MODELS: GEC3-12 AND GES3-12 ONLY
To remove bezel, grip
both sides of bezel
and pull in a
downward and
outward motion.
Candela selection
slider switch. Depress
center and slide switch to
desired brightness level.
Break off pin and insert
into hole at the bottom of
the selector to lock candela
setting. Signal must be
removed from bracket and
pin pushed forward from
backside out of hole to
change candela.
SWITCH POSITION
TONE
3
4
5
Mechanical Temporal 3
ON
ON
ON
Mechanical - Continuous
OFF
ON
ON
2400Hz - Temporal 3
ON
OFF
ON
2400Hz - Continuous
OFF
OFF
ON
Chime - Temporal 3
ON
ON
OFF
Chime - Continuous
OFF
ON
OFF
Whoop
ON
OFF
OFF
Whoop
OFF
OFF
OFF
NOTICE
:
w
SWITCH POSITIONS 1 AND 2 IN THE OFF POSITION TO
SELECT ISOLATED HORN AND STROBE POWER INPUTS
w
SWITCH POSITION 6 ON = HIGH DBA
w
SWITCH POSITION 6 OFF = LOW DBA
THIS APPLIANCE WILL NOT OPERATE WITHOUT ELECTRICAL POWER. AS FIRES FREQUENTLY CAUSE POWER INTERRUPTIONS,
GENTEX SUGGESTS YOU DISCUSS FURTHER SAFEGUARDS WITH YOUR LOCAL FIRE PROTECTION SPECIALIST.
CAUTION:
A jumper card is provided to test for
correct wiring in the supervisory mode only.
DO NOT pass alarm current through the jumper.